BACnet interoperability building blocks supported (Annex K) - Basic Documentation - GDB181.1E/BA - GDB181.1EMBA - GLB181.1E/BA

GxB181.1E/BA - VAV Compact Controller BACnet MS/TP -BACnet Protocol Implementation Conformance Statement (PICS)

Product Family
OpenAir
Product Group
Damper actuators
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2015-08-24
Document No
A6V10644636_en--_a
Download ID
A6V10683630
Stock No.
S55499-D506
S55499-D168
S55499-D169
Product No.
GDB181.1E/BA
GDB181.1EMBA
GLB181.1E/BA
Access level
Internet
File Type
html
md

Data sharing

🞎 Data Sharing – Read Property-A DS-RP-A

πŸ—·

Data Sharing – Read Property-B DS-RP-B
🞎 Data Sharing – Read Property Multiple-A DS-RPM-A

πŸ—·

Data Sharing – Read Property Multiple-B DS-RPM-B
🞎 Data Sharing – Write Property-A DS-WP-A

πŸ—·

Data Sharing – Write Property-B DS-WP-B
🞎 Data Sharing – Write Property Multiple-A DS-WPM-A
πŸ—· Data Sharing – Write Property Multiple-B DS-WPM-B
🞎 Data Sharing – Change of Value -A DS-COV-A
πŸ—· Data Sharing – Change of Value -B DS-COV-B
🞎 Data Sharing – Change of Value Property -A DS-COVP-A
🞎 Data Sharing – Change of Value Property -B DS-COVP-B
🞎 Data Sharing – Change of Value-Unsolicited-A DS-COVU-A
🞎 Data Sharing – Change of Value-Unsolicited-B DS-COVU-B
🞎 Data Sharing – View-A DS-V-A
🞎 Data Sharing – Advanced View-A DS-AV-A
🞎 Data Sharing – Modify-A DS-M-A
🞎 Data Sharing – Advanced Modify-A DS-AM-A

Alarm and event management

🞎 Alarm and Event – Notification-A AE-N-A
🞎 Alarm and Event – Notification Internal-B AE-N-I-B
🞎 Alarm and Event – Notification External-B AE-N-E-B
🞎 Alarm and Event – ACK-A AE-ACK-A
🞎 Alarm and Event – ACK-B AE-ACK-B
🞎 Alarm and Event – Alarm Summary-B AE-ASUM-B
🞎 Alarm and Event – Enrollment Summary-B AE-ESUM-B
🞎 Alarm and Event – Information-B AE-INFO-B
🞎 Alarm and Event – Life Safety-A AE-LS-A
🞎 Alarm and Event – Life Safety-B AE-LS-B
🞎 Alarm and Event – View Notifications-A AE-VN-A
🞎 Alarm and Event – Advanced View Notifications-A AE-AVN-A
🞎 Alarm and Event – View and Modify-A AE-VM-A
🞎 Alarm and Event – Advanced View and Modify-A AE-AVM-A
🞎 Alarm and Event – Alarm Summary View-A AE-AS-A
🞎 Alarm and Event – Event Log View-A AE-ELV-A
🞎 Alarm and Event – Event Log View and Modify-A AE-ELVM-A
🞎 Alarm and Event – Event Log Internal-B AE-EL-I-B
🞎 Alarm and Event – Event Log External-B AE-EL-E-B

Historical/Deprecated BIBBs

Alarm and event management

🞎 Alarm and Event – Alarm Summary-A AE-ASUM-A
🞎 Alarm and Event – Enrollment Summary-A AE-ESUM-A
🞎 Alarm and Event – Information-A AE-INFO-A

Scheduling

🞎 Scheduling – Internal-B SCHED-I-B
🞎 Scheduling – External-B SCHED-E-B
🞎 Scheduling – Advanced View Modify-A SCHED-AVM-A
🞎 Scheduling – View Modify-A SCHED-VM-A
🞎 Scheduling – Weekly Schedule-A SCHED-WS-A
🞎 Scheduling – Weekly Schedule Internal-B SCHED-WS-I-B
🞎 Scheduling – Readable-B SCHED-R-B


Historical/Deprecated BIBBs

🞎 Scheduling – A SCHED-A

Trending

🞎 Trending – Viewing and Modifying Trends-A T-VMT-A
🞎 Trending – Viewing and Modifying Internal-B T-VMT-I-B
🞎 Trending – Viewing and Modifying External-B T-VMT-E-B
🞎 Trending – Viewing and Modifying Multiple Values-A T-VMMV-A
🞎 Trending – Viewing and Modifying Multiple Values Internal-B T-VMMV-I-B
🞎 Trending – Viewing and Modifying Multiple Values External -B T-VMMV-E-B
🞎 Trending – Automated Multiple Value Retrieval-A T-AMVR-A
🞎 Trending – Automated Multiple Value Retrieval-B T-AMVR-B
🞎 Trending – View-A T-V-A
🞎 Trending – Advanced View and Modify-A T-AVM-A
🞎 Trending – Archival-A T-A-A
🞎 Trending – Automated Trend Retrieval-A T-ATR-A
🞎 Trending – Automated Trend Retrieval-B T-ATR-B


Historical/Deprecated BIBBs

🞎 Trending – Viewing and Modifying Trends-A T-VMT-A
🞎 Trending – Viewing and Modifying Multiple Values-A T-VMMV-A

Device management

🞎 Device Management – Dynamic Device Binding-A DM-DDB-A
πŸ—· Device Management – Dynamic Device Binding-B DM-DDB-B
🞎 Device Management – Dynamic Object Binding-A DM-DOB-A
πŸ—· Device Management – Dynamic Object Binding-B DM-DOB-B
🞎 Device Management – Device Communication Control-A DM-DCC-A
πŸ—· Device Management – Device Communication Control-B DM-DCC-B
🞎 Device Management – Private Transfer-A DM-PT-A
🞎 Device Management – Private Transfer-B DM-PT-B
🞎 Device Management – Text Message-A DM-TM-A
🞎 Device Management – Text Message-B DM-TM-B
🞎 Device Management – Time Synchronization-A DM-TS-A

Device management

🞎 Device Management – Time Synchronization-B DM-TS-B
🞎 Device Management – UTC Time Synchronization-A DM-UTC-A
🞎 Device Management – UTC Time Synchronization-B DM-UTC-B
🞎 Device Management – Reinitialize Device-A DM-RD-A
πŸ—· Device Management – Reinitialize Device-B DM-RD-B
🞎 Device Management – Backup and Restore-A DM-BR-A
🞎 Device Management – Backup and Restore-B DM-BR-B
🞎 Device Management – Restart-A DM-R-A
🞎 Device Management – Restart-B DM-R-B
🞎 Device Management – List Manipulation-A DM-LM-A
🞎 Device Management – List Manipulation-B DM-LM-B
🞎 Device Management – Object Creation and Deletion-A DM-OCD-A
🞎 Device Management – Object Creation and Deletion-B DM-OCD-B
🞎 Device Management – Virtual Terminal-A DM-VT-A
🞎 Device Management – Virtual Terminal-B DM-VT-B
🞎 Device Management – Automatic Network Mapping-A DM-ANM-A
🞎 Device Management – Automatic Device Mapping-A DM-ADM-A
🞎 Device Management – Automatic Time Synchronization-A DM-ATS-A
🞎 Device Management – Manual Time Synchronization-A DM-MTS-A

Network management

🞎 Network Management – Connection Establishment-A NM-CE-A
🞎 Network Management – Connection Establishment-B NM-CE-B
🞎 Network Management – Router Configuration-A NM-RC-A
🞎 Network Management – Router Configuration-B NM-RC-B