Error flag |
Reason |
Solution |
---|---|---|
'MC link not enabled' message in the 'Sinteso Test' app |
MC link is not activated on the station. |
|
The detector exchanger and tester has been removed from the device too early. |
| |
No confirmation from the system |
| |
'Element not found on station' message in the 'Sinteso Test' app |
An incorrect site configuration has been loaded to the 'Sinteso Test' app. |
|
The group or logical channel selected in the 'Sinteso Test' app belongs to a different station than the device to which the detector exchanger and tester is connected. |
| |
Confirmation of assignment required in Sinteso Test |
The logical channel has already been assigned |
If the logical channel has already been assigned to a different device, 'Sinteso Test' suggests a new assignment. The new assignment must be confirmed manually in 'Sinteso Test'. The old assignment is deleted. |
An MC link error is displayed |
The detectors have been mounted in close proximity to one another – e.g., on a detector board for testing or training purposes. |
Increase the distance between the detectors. |
The wrong detector is assigned to the zone. |