The data saved in the XML file is displayed by 'Sinteso Test' and the peripheral device is marked as tested if one of the following commands is executed successfully with detector exchanger and tester FDUD292:

  • '2.2 Check + ALARM'
  • '2.3 Check+Testalarm'
  • '2.4 ALARM'
  • '2.5 Test Alarm'
  • '2.6 Test Alarm Total'
  • '2.7 Chk+Test Al. Tot.'

You will find more information about executing the commands in document 007227.

Calling up data from the detection tree

  • The detector exchanger and tester has been connected to 'Sinteso Test'.
  • The XML file for the site has been imported into 'Sinteso Test'.
  • Execute one of the commands listed above with the detector exchanger and tester.
  • If the command is executed successfully, 'Sinteso Test' marks the peripheral device as 'Manually Tested'.
  • If the command is executed successfully, 'Sinteso Test' displays the detailed view with the data from the detection tree.
  • If voice output is activated, the data from the detection tree is read out.