Problem | Solution |
---|---|
When the XML file is exported from SintesoWorks, the '/Documents/Sinteso Test' style sheet is not found. |
|
The connection to the Bluetooth extension kit is not restored when you open 'Sinteso Test'. | Switch the Bluetooth function on the smartphone off and on again. |
Switch the smartphone off and on again. | |
Check the charge of the detector exchanger and tester battery and insert a new battery if necessary. | |
When you open the detailed view, the following message appears on the smartphone: 'Your device does not have the necessary software installed to read in the selected language. Do you want to install it from the play store?'. | Install a file with the voice data for the 'Text-to-Speech Output' function of your smartphone. |
The font in the detailed view is too large. | Reduce the font size in the system settings for the smartphone. |
The voice output is difficult to understand. | Reduce the voice output speed in the system settings for the smartphone. |
Combinations of uppercase letters are read out as letters rather than words. | In the 'Settings' view, deactivate the 'Spell all-capital words' checkbox under 'Sound volume'. |
The symbol for the Bluetooth extension kit is not displayed. | Check whether the Bluetooth extension kit is switched on and execute the command '8.2 Enable' if necessary. |
Switch the service device off and on again. | |
Check whether the 10-pin connector for the Bluetooth extension kit has shifted and reinsert the 10-pin connector if necessary. See document A6V10405496. | |
The app crashes repeatedly with certain functions. |
|