Apply a saved User Setting to multiple stations of the same station type.

  1. Make sure the all stations have the correct station ID (a later change of the station ID will reset it to factory reset and it will lose all configuration).
  1. Select ‘Station’ > ‘User Settings’ > ‘<root>’, select the appropriate User settings file, select ‘Apply to…’
  1. In the pop-up window specify the criteria for the stations and the stations which should be configured.
Apply User settings to multiple stations

Note:

With preconfigured settings you have to take care that no cross-station IDs are used for functions, macros, inputs and outputs. These can be prevented e.g. with using "<Me>...", but must be finally configured after applying the User Setting.