The 'Bus Devices Firmware update...' function updates the firmware of the 'PACE-Bus' (RS485) components.
This function is only enabled for the 'PACE-Bus' (RS485) components.
Display the information for all connected 'PACE-Bus' components by using the station function 'Station' > 'Get Bus Info' (Versions).
- Select a station in the 'System Overview' tab to update the 'PACE-Bus' components connected to this station.
- Click on the icon to start the 'PACE-Bus' components firmware update wizard.
- Choose the file to update the connected component.
- PT1002 requires 2 firmware updates – one for the operating part and one for the call station part.
- Start the firmware update. A status dialog pop-up window shows the status of the firmware update.
- This can take a while especially when several 'PACE-Bus' components are connected.
- At the end of the update a result dialog window will show the results of the update
File name | Use for 'PACE-Bus' components |
---|---|
BusDevice_Type01_UPD_Vx.y.hex | PT2006 |
BusDevice_Type02_IO_Vx.y.hex | PCIO2001 |
BusDevice_Type03_IO2_Vx.y.hex | PCIO2002 with PCIO2003 PCO2002 with PCIO2003 |
BusDevice_Type04_CS18_Vx.y.hex | PT2009 with PTO2006 PT1002 (call station part) |
BusDevice_Type05_FF_Vx.y.hex | PT2003 |
BusDevice_Type06_VACP_Vx.y.hex | PT2010 PT1001 PT1002 (operating part) |
Closing the status dialog pop-up window doesn't affect the update process. The result dialog window will not be shown at the end of the process.