A logic control output should be controlled from two separate call stations. The LED of the function key should light up if the status is (ON).
Configuration of call station A:
- Configure a keypad button with the function 'Switch L>H' (acts as a common status indicator, sharing the boolean information OFF/ON).
- Configure a keypad button with the function 'Macro mode' and enable the 'USE_MACROS' flag.
Setting macros for the PRESS event
'LedState' of call station A, 'any LED' set to 'Switch L>H'
'Emulate Key' of call station A set to 'Switch L>H'
Setting macros for the RELEASE event
'Emulate Key' of call station A set to 'Switch L>H'
'Emulate Key' of call station B set to 'Macro Mode'
Configuration of call station B:
- Configure a keypad button with the function 'Macro mode' and enable the 'USE_MACROS' flag.
Setting macros for the PRESS event
'LedState' of call station A, 'any LED' set to 'Switch L>H'
'Emulate Key' of call station A set to 'Switch L>H'
Setting macros for the RELEASE event
'Emulate Key' of call station A set to 'Switch L>H'
'Emulate Key' of call station A set to 'Macro Mode'
Configuring a logic control output for a digital audio matrix:
- Activate the 'Enabled' checkbox.
- Set the function to 'Keypad Led'.
- Set 'Station' to the station ID of call station A.
- Right-click in the field 'LED Index Field' (default value = 1) and set to 'Switch L>H'.