Chapter 8.7 in EN 54-16
8.7.1: 'Indications of faults as required in 8.2 shall be capable of being reset:
- Automatically when faults are no longer recognized
- And/or
- By a manual operation at access level 2.'
Configuring the logic control input accordingly
- Enable the desired logic control input, and define it as follows:
- 'EN54-16: System Fault reset'