EN 54-16, chapter 7.7.2

7.7.2.1: 'It shall be possible to reset the voice alarm condition from the VACIE at access level 2 by means of a separate manual control. In this case, this control shall be used only for reset and may be the same as that used for reset from the fault warning condition.'

7.7.2.2: 'Following a manual reset operation, the indication of the correct functional condition corresponding to any received signals shall either remain or be re-established within 20 s.'

Configuring the logic control inputs accordingly

  • Enable the desired logic control input, and define it as follows:
  • 'Alarm Stop'