- Three remote control panels are connected to a PC2001 'Digital audio matrix (4/4/4)'.
- Panel 2 should be able to control outputs 1+2 at the same time.
- Panel 3 should be able to control either output 3 or output 4.
- Panel 10 should be able to control each output individually.
- All panels are able to choose from the same channel list: '100 Tuner', '101 CD'.
Preset 1
Name | Value | Remark |
---|---|---|
Allowed views | Vol and Ch +/- | Common for all presets |
Station ID | 507 | Common for all presets |
Audio Outputs | 1 + 2 | Route this to ID 2 |
Channels | 100, 101 | Common for all presets |
Preset 2
Name | Value | Remark |
---|---|---|
Allowed views | Not used | Not required, as already specified under Preset 1. This configuration can be reused. |
Station ID | Not used |
|
Audio Outputs | 3 + 4 + cycle through outputs | Route this to ID 3 |
Channels | Not used |
|
Preset 3
Name | Value | Remark |
---|---|---|
Allowed views | Not used |
|
Station ID | Not used |
|
Audio Outputs | 1 + 2 + 3 + 4 + cycle through outputs | Route this to ID 10 |
Channels | Not used |
|
Panel specific configuration
'Device ID' | 2 | ||
Set | Vol and Ch +/- | Of station | 507 |
Audio feed | 100, 101 | Channels | 1 + 2 |
'Device ID' | 3 | ||
Set | Vol and Ch +/- | Of station | 507 |
Audio feed | 100, 101 | Channels | 3 + 4 + cycle |
'Device ID' | 10 | ||
Set | Vol and Ch +/- | Of station | 507 |
Audio feed | 100, 101 | Channels | 1 + 2 + 3 + 4 + cycle |