Configuring desk call station PT2008Check the jumper configuration on the Call station PCB
- Supply EXT: supply voltage is taken from +10 V logic supply
- 'MIC' > 'Out': if both jumpers are set, the transmitted signal level is MIC (default).
- 'MIC' > 'Out': if both jumpers are cleared, the transmitted signal level is LINE.
- No Mute: if the jumpers are cleared, this will mute the microphone signal if the TALK button is not pressed (default).
- No Mute: if the jumpers are set, this will always transmit the microphone signal
Setup the analog audio input
- Set 'Default MIC level' for the analog audio input level and set the input gain to +40 dB.
- Values may vary dependent on the length of the network cable used
- Disable the phantom power
- Configure the first analog audio input ('IN1') of the digital audio matrix as the priority channel by assigning a channel number >128.
Setup a virtual call station
- Open the configuration page 'Station' > 'Configure Virtual Keypad'
- Configure 3 'ZONE SELECT' buttons and 1 'TALK' button
- Optional test the interface with virtual emulate keypad functionality
Setup the logic control inputs
- Open the configuration page 'Digital Inputs' > 'Logic Inputs (Connector)'
- Enable four logic control inputs and set the functions according to the screenshot.
- Assign the 'Keypad ZONE SELECT' > 'Key ID' to the virtual call stations' zone buttons you have already configured.
- Enable the 'GP' flag for every 'Keypad ZONE Select' input.
- Assign the 'Emulate Keypad Key' > 'Key ID' to the 'Talk' button of the virtual call station