Power supply

Operating voltage

SAX31..

AC 230 V ± 15 %

SAX61..

AC 24 V ± 20 % / DC 24 V + 20 % / - 15 % (SELV / PELV)

SAX81..

External supply line fusing (EU)

  • Non-renewable fuse 6...10 A slow
  • Circuit break max. 13 A, tripping characteristic B, C, D to EN 60898
  • Power source with current limitation of max. 10 A

Fusing per DIN 57100 part 430 (supply line)

6...10 A slow

Typical inrush current 1)
(3-position actuators)

SAX31..

2.3A

SAX81..

4.5A

Functional data

Positioning time for nominal stroke

The positioning time may vary depending on the type of valve
(Type summary)

SAX31.00, SAX81.00

120 s

SAX31.03, SAX61.03.., SAX81.03..

30 s

Positioning force

800 N

Nominal stroke

20 mm

Working stroke range at which the actuator is calibrated

8...23 mm

Permissible media temperature (valve fitted)

-25...130 °C

Signal Inputs

Positioning signal ”Y”

SAX31.., SAX81..

3-pos.

SAX31.. Voltage

AC 230 V ± 15 %

SAX81.. Voltage

AC 24 V ± 20% / DC 24 V + 20% / - 15%

SAX61.. (DC 0...10 V) current draw

≤ 0.1 mA

Input impedance

≥100 kΩ

SAX61.. (DC 4…20 mA) current draw

DC 4...20 mA ± 1%

Input impedance

≤ 500 Ω

Power consumption at 50 Hz

Type

Item NO.

Operating [W]

Operating [VA]

Standby [W]

Standby [VA]

SAX31.00

S55150-A105

2.2

3.9

1.3

2.2

SAX31.03

S55150-A106

4.6

7.9

1.3

2.2

SAX61.03

S55150-A100

2.5

6.3

1.7

4.6

SAX61.03U

S55150-A100-A100

2.5

6.3

1.7

4.6

SAX61.03/MO

S55150-A140

3.0

7.0

2.2

6.0

SAX81.00

S55150-A102

2.3

4.0

1.5

2.7

SAX81.03

S55150-A103

4.3

7.2

1.5

2.6

SAX81.03U

S55150-A103-A100

4.3

7.2

1.5

2.6

Communication

Communication protocol

Modbus RTU

RS-485, not galvanically isolated

Number of nodes

Max. 32

Address range

1...245 / 255

Factory setting

255

Transmission formats

1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2

Factory setting

1-8-E-1

Baud rates (kbaud)

Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2

Factory setting

Auto

Bus termination

120 Ω electronically switchable

Factory setting

Off

Parallel connection

SAX61..

≤ 10 (depending on controller output)

Forced control

Z positioning signal

SAX61..

R = 0...1000 Ω, G, G0

R = 0...1000 Ω

Stroke proportional to R

Z connected to G

Max. stroke 100 % 2)

Z connected to G0

Max. stroke 0 % 2)

Voltage

Max. AC 24 V ± 20 %

Max. DC 24 V + 20 % / - 15 %

Current draw

≤ 0.1 mA

Position feedback

U

Voltage range SAX61..

0...10 V DC

Load impedance

> 10 kΩ resistive

Load

Max. 1 mA

Connection cable

Wire cross-sectional areas

0.13...1.5 mm 2, AWG 24...16 3)

Cable entries

SAX.. (EU)

2 entries ∅ 20.5 mm (for M20)

1 entry ∅ 25.5 mm (for M25)

SAX..U (US)

3 entries ∅ 21.5 mm for ½” tube connection

SAX61../MO

Fixed connection cable 0.9m

Number of cores 5 x 0.75 mm 2

Degree of protection and class

Housing from vertical to horizontal

IP 54 as per EN 60529 4)

Device protective class per
EN 60730-1

SAX31.. AC 230 V

II

SAX61.. AC / DC 24 V

III

SAX81.. AC / DC 24 V

Environmental conditions

Operation per
IEC 60721-3-3

Climatic conditions

Class 3K5

Mounting location

Indoors (weather-protected) 4)

Temperature, general

-5...<55 °C

Humidity (non-condensing)

5...95 % r.h.

Transport per
IEC 60721-3-2

Climatic conditions

Class 2K3

Temperature

-25...70 °C

Humidity

5...95 % r.h.

Storage per
IEC 60721-3-1

Climatic conditions

Class 1K3

Temperature

-15...55 °C

Humidity

5...95 % r.h.

Max. media temperature when mounted on valve

130 °C

Directives and standards

Product standard

EN 60730-x

Electromagnetic compatibility (field of use)

For residential, commercial, and industrial environments

EU conformity (CE)

See EU declaration of conformity CE1T4501X1 5)

UK conformity (UKCA)

See UK declaration of conformity A5W00185581A-001 5)

RCM compliance

See RCM declaration of conformity CE1T4515X4 5)

EAC compliance

Eurasian compliance for all SAX..

UL, cUL

AC 230 V

-

AC / DC 24 V

UL 873 http://ul.com/database file number E35198

Environmental compatibility

Product environmental declarations 71 7331 0559 5) und A6V101083254 5) include data on environmentally friendly product design and testing (RoHS compliance, material composition, packaging, environmental benefits, disposal).

Dimensions

See Dimensions

Accessories

Potentiometer ASZ7.5 6)
0...1000 Ω ± 5 %

Voltage

DC 10 V

Current rating

< 4 mA

Auxiliary switch ASC10.51 6)

Switching capacity

AC 24…230 V, 6 (2) A, potential free

External fusing of supply line

  • Non-renewable fuse 6...10 A slow
  • Circuit break max. 13 A, tripping characteristic B, C, D to EN 60898
  • Power source with current limitation of max. 10 A

US installation, UL & cUL

AC 24 V class 2, 5 A general purpose

Stem heating element ASZ6.6

Operating voltage

AC / DC 24 V ± 20 %

Power draw

50 VA, 30 W

Inrush current (cold)

Max. 8.5 A (max. temperature 85 °C/185 F)

1)

Switching time for RMS value of the sine wave at nominal voltage

2)

Observe acting direction of DIL switches

3)

AWG = American wire gauge

4)

For outdoor operation, always use weather shield ASK39.1, housing protection class IP 54 remains as is.

SAX61../MO is not intended for outdoor use.

5)

Documents can be downloaded at https://www.siemens.com/bt/download.

6)

UL-approved components