1. The alarm current of ABHW-4S has to be energized by any UL listed 24 VDC regulated auxiliary power supply including the aux power output of XLS/Desigo Fire Safety Modular/Cerberus PRO Modular, FC2005/FC901, FC2025/ FC2050/FV2025/FV2050, FC922/FC924/FV922/FV924 and 3 PAD-3/PAD-4/PAD-5 (refer to Figure 1), ZIC-4A (FireFinderXLS/Desigo Fire Safety Modular/Cerberus PRO Modular zone indicating card (NAC), refer to Figure 3), PAD-3/ PAD4/PAD-5 (Figure 4), or a 24 VDC NAC circuit such as FC2005/ FC901 (Refer to Figure 5) or NAC circuit such as FC2025/FC2050/FV2025/FV2050, FC922/FC924/FV922/ FV924 (Refer to Figure 6).
  2. The alarm current of ABHW-4S CANNOT be energized by a 24 V FWR power supply.
  3. The maximum number of ABHW-4S is related to the maximum current rating and the power line resistance of the auxiliary power supplies applied on the ABHW-4S. Refer to the related installation instructions of the auxiliary power supply.
  4. The maximum loop line resistance cannot exceed the maximum line resistance defined in the compatible fire control panels.
  5. T-tapping of the notification appliance circuit is not allowed.
  6. The NAC output must be set to a steady DC if it is used for ABHW-4S.