The alarm current of ABHW-4S has to be energized by any UL listed 24 VDC regulated auxiliary power supply including the aux power output of XLS/Desigo Fire Safety Modular/Cerberus PRO Modular, FC2005/FC901, FC2025/ FC2050/FV2025/FV2050, FC922/FC924/FV922/FV924 and 3 PAD-3/PAD-4/PAD-5 (refer to Figure 1), ZIC-4A (FireFinderXLS/Desigo Fire Safety Modular/Cerberus PRO Modular zone indicating card (NAC), refer to Figure 3), PAD-3/ PAD4/PAD-5 (Figure 4), or a 24 VDC NAC circuit such as FC2005/ FC901 (Refer to Figure 5) or NAC circuit such as FC2025/FC2050/FV2025/FV2050, FC922/FC924/FV922/ FV924 (Refer to Figure 6).
The alarm current of ABHW-4SCANNOT be energized by a 24 V FWR power supply.
The maximum number of ABHW-4S is related to the maximum current rating and the power line resistance of the auxiliary power supplies applied on the ABHW-4S. Refer to the related installation instructions of the auxiliary power supply.
The maximum loop line resistance cannot exceed the maximum line resistance defined in the compatible fire control panels.
T-tapping of the notification appliance circuit is not allowed.
The NAC output must be set to a steady DC if it is used for ABHW-4S.