Use a 30-foot center spacing (900 sq ft), as a starting point referred to in NFPA Standard 72 National Fire Alarm Code and CAN/ULC-S524, in a detector installation layout. This spacing is based on ideal conditions—smooth ceiling, no air movement, and no physical obstructions. In all installations (except in special circumstances like computer room under floors), locate the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, between 4 and 6 inches from the ceiling.

If questions arise regarding detector placement, it is extremely important that the drawings provided or approved by Siemens Industry, Inc., or by its authorized distributors be followed. The detector placements shown on these drawings were chosen after careful evaluation of all facets of protecting the area. Environmental factors such as air current, temperature, humidity, air pressure, and the nature of the fire load are carefully considered. Special consideration is given to room or area configuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Industry, Inc.'s extensive experience in the design of fire detection systems assures optimum detector placement and is reflected in these drawings. Follow sound engineering judgment made by qualified personnel.