1. The max. number of loop powered ABHW-4B audible bases in one device loop depends on the available load current for ABHW-4B audible bases. The available load current for loop powered ABHW-4Bs (I) can be calculated by:
I = Imax – Id
In which, Imax is the max load current in one loop under the worst-case scenario with 50 Ω cable resistance. Id is the total load current for the devices loaded in the loop.

Max. number of loop powered ABHW-4B in high dBA
Max. number of loop powered ABHW-4B in low dBA

2. The max. number of loop powered ABHW-4B for the worst-case scenario (All detectors wired at the end of 50 ohm cable)

Detector Loaded in one DLC

Current available for ABHW-4B

Max number of loop powered ABHW-4B

 

High dBA

Low dBA

252 FD-UL detectors

181 mA

24

40

252 H-series detectors

Note

Note

Note

100 FD-UL detectors and 152 H-detectors

110 mA

14

24

Loop power cannot be used for ABHW-4B with H-series detectors; the external power must be used.

3. How to calculate the max. number of loop powered ABHW-4B.

Step 1:

Calculate the total load current (Id) for the devices loaded in the device line using the current rating of each device including accessories.
Example:
Current load of 100 FDOT421 detectors = 0.28 mA*100 = 28 mA
Current load of 152 HFP-11 detectors = 0.75 mA*152 = 114 mA

Step 2:

Find out the max. device load current (Imax) of device line card at worst case from the user manual of the panel.
Example: For DLC in XLS systems, XDLC in Desigo Fire Safety Modular/Cerberus PRO Modular systems, 252 H-series devices can be loaded at the end of 50 ohms max. line resistance (the worst case) and max. load current is 252 mA (Imax).

Step 3:

Find out the available load current (I) for loop powered ABHW-4B audible bases.
I = Imax – Id
Example: If 100 FDOT421/OH921 and 152 HFP-11 detectors are loaded at the end of a 50 ohm cable, I=252–142 = 110 mA

Step 4:

Find out the max. alarm current rating for the loop powered ABHW-4B (Ia). Find out the max. number of the loop powered ABHW-4B using the charts above, or it is equal to (I/Ia).
Example: If all ABHW-4Bs are set to Low volume, the max. number of loop powered ABHW-4Bs is 24 (from Figure 13). The max. current rating of ABHW-4B is 4.5mA (from electronic ratings). The max. number of loop powered ABHW-4Bs is equal to 110 mA/4.5 mA=24. If all ABHW-4Bs are set to high volume, the max. number of loop powered ABHW-4Bs is 14 (from Figure 12). The max. current rating of ABHW-4B is 7.5 mA. The max. number of loop powered ABHW-4Bs is equal to 110 mA/7.5 mA=14.