Flow measuring section

  • Can be installed in any position.
  • The mounting location (return) must be in accordance with the type of meter used.
NOTICE

Always install the flow measuring section in the return on types UH50-A.., UH50-C.., and UH50-G...

  • Settling paths are not required, neither upstream of nor downstream from the meter.
  • Thoroughly flush the plant prior to installing the meter.
  • Mount the flow measuring section between 2 shutoff valves with the arrow pointing in the direction of flow.
  • The sensors must be mounted in the same water circuit as the flow measuring section (observe mixing).
  • Do not separate, shorten, or extend the lines.
  • Connect the individual wires according to the wiring diagram printed on the meter.
  • The sensors can be fitted in T-pieces or ball valves, or can be immersed, either directly or in pockets (observe all national regulations).
NOTICE

In Germany, the temperature sensors must be installed submerged for meters to qp 6 and to PN16.

  1. Immersion sleeves are only needed in the case of higher stress levels.
  • The end of the sensors’ probe must extend to at least the pipe center.
  • Temperature sensors and fittings must be sealed to prevent tampering.
  • Overpressure must prevent cavitation across the entire measuring range, that is, at least 1 bar with qp and approximately 3 bar with qs (at 80 °C).
  • Only authorized personnel are allowed to remove and replace calibration seals when carrying out service work.

Ball valve

Example of mounting with a ball valve (recommended up to qp 6)

Welded sleeve with protection pocket

Example of mounting with protection pockets (recommended above qp 10)

Required position for the cooling energy meter

  • To avoid condensation on cooling energy or combined heat/cooling energy meters, make sure the black cover on the measuring tube points to the side or downward.
  • Install the protection pockets so that the temperature sensor is horizontal or vertical, pointing down.
  • Mount the processor unit away from the flow measuring section (e.g. on the wall) and ensure that condensation cannot run along the connected lines, entering the processor unit (forming a loop downward).

1

Transducer cover

Permissible mounting position when metering cooling energy

Processor unit

  • The ambient temperature of the processor unit cannot exceed 55 °C.
  • Avoid direct sunlight.
  • Ensure that no water can enter the processor unit at the mounting location.

Proceed as follows to mount the processing unit:

  • Remove the unit from the flow measuring section
  • Screw the adapter plate for the flow measuring section
  • Screw the adapter plate to the wall
  • Slide the processor unit to the adapter base

 

NOTICE

On models with removable control wiring, you can disconnect and reconnect the wiring during installation.

  1. Connect only paired parts (volume measuring section, processor unit) when reconnecting.
  1. Note the correct pin assignment.
  1. Do not extend nor shorten the control wiring.