Metering accuracy as per EN 1434

The diagram below shows the typical metering accuracy of the UH50.., compared to the error limits per EN 1434, class 2.

Key:

EN 1434, class 3

EN 1434, class 2

UH50.. typical (EN 1434, ½ class 2)

q

Current flow that determines the precision as a percentage of the continuous flow qp

qi

Lower flow limit (value 1 on the x axis = 1 % of qp):
The smallest flow above which the heat meter must operate without exceeding the fault limits.

qp

Continuous flow of meter = Value 100 on the x axis.

The pressure loss in a flow sensor is indicated as continuous flow qp.

Actual pressure loss at the indicated flow can be calculated using the Kv value, which indicates flow at 1 bar differential pressure:

 

Δp = Pressure loss in bar

Q = Flow in m3 / h

Kv = Kv – Value at Δp = 1 bar

Continuous flow qp

m3/h

Mounting length

mm

Connection

Pressure loss at qp

mbar

Kv value at Δp = 1 bar

m3/h

Curve in the diagram

0.6

110, 190

G ¾, G 1, DN20

150

1.5

A

1.5

130, 190

G 1, DN20

160

3.8

B

1.5

110

G ¾

150

3.9

C

2.5

190

G 1, DN20

210

5.3

D

2.5

130

G 1

200

5.6

E

3.5

260

G 1¼, DN25

55

15

G

6

150

G 1¼

190

14

F

6

260

G 1¼, DN25

140

16

H

10

200, 300

G 2, DN40

130

28

I

10

300

G 2

110

30

J

15

270

DN50

110

45

K

15

200

DN50

95

49

L

25

300

DN65

105

77

M

40

300

DN80

160

100

N

60

360

DN100

115

177

O

150

500

DN150

120

433

P

The value can also be read graphically using the diagram as an alternative.

Pressure drop characteristic

Display

The meter displays current readings in kWh, MWh, MJ or GJ.

You can only select between kWh or MWh and MJ or GJ on the meter.

*) Decimal places "flashing", "static", or "suppressed"

The decimal places of displayed values are outlined to avoid errors.

Calibrated values are identified by a star symbol.

1

Decimal places outlined

2

Calibrated value

The number of decimal places of a value depends on the selected measuring path and the selected unit.

The meter’s displays are arranged in 5 loops:

  • 1 user loop
  • 4 service loops

1

Display

2

Button 1

3

Button 2

4

Optical interface

5

Calibration seal

 

 

A short press on button 1 enables selection of the required loop. The user loop reappears after the last loop. Press button 2 to read the value on the respective loop. The first value reappears after the last loop.

The range of display and the displayed data may deviate from this description and certain button functions may be disabled, depending on the parameter settings on the meter.

User loops

Detailed information on user loops is available under 'Product documentation’ data sheet CE2B5324.

 

Error codes

Detailed information on error codes is available under 'Product documentation’ data sheet M5324.

 

Standard parameters

It is programmed at the factory as follows:

  • Set day [TT.MM]: 01.01

Power supply

The UH50.. can be powered by a power supply or battery.

Automatic mains detection

The power supply detects whether line voltage is present. The signal is provided to the UH50... The device automatically detects whether it is powered by a battery or a power supply.

 

Power packs

 

 

Power pack AC/DC 24 V

WZU-ACDC24-50

Power pack AC 110/230 V

WZU-AC110/230-15

WZU-AC110/230-50

Batteries

Standard battery (2 AA)

WZU-BA+GUM

Universal battery with compartment for UN50.. And UC50..

WZU-BD-HALT

 

Battery with compartment for NB IoT module

 

Battery life

Battery life depends on the type of battery and requirements
(e.g. short time base, analog module, etc.).

NOTICE

Install only batteries approved by the manufacturer.

Requirements

(with time base Q = 4 s and T = 30 s)

6 years

11 years

16 years

Power supply
AC 110/230 V;

AC / DC 24 V

Pulse module
(standard pulses)

M-bus module G4

(Normal read mode 15 min.)

BACnet/Modbus module

(Read > 10 min.)

2x AA

C

D

Yes

RF module 868 MHz
(stationary 15 min. transmission interval)

D

D

D

Yes

RF module 868 MHz
(mobile 16 sec. transmission interval)

D

D

‑

Yes

RF module LoRaWAN

*) In Eco mode
Transmission interval for 11 year lifecycle: 60 min.
Transmission interval for 16 year lifecycle: 160 min.

**) Powerpack: AC 110/230 V only

-

D *)

D *)

Yes **)

RF module NB IoT-G2, band 3, 8, 20
***) and auxiliary battery for NB IoT (WZU-NB-IoT-BAT)

-

C ***)

-

Yes

M-bus module G4

(Fast read mode 4 sec.)

Pulse module

(Fast pulses)

Analog module

BACnet/Modbus module

(Read < 10 min.)

D

‑

‑

Yes

Fast time base
(with time base 
Q = 4 s and T = 4 s)

D

‑

‑

Yes

 

The following table displays the modules requiring an external power supply.

Module

Type of power supply

BACnet/Modbus module

AC/DC 24 V, e.g. WZU-NE24

Analog module

AC/DC 24 V, e.g. WZU-NE24

Communication

Communication module

The communication modules are connected via a 6-pole reaction-free plug, enabling them to be installed or replaced at any time.

Compliance with ESD regulations must be ensured.

1

Module 1

2

Module 2

The UH50.. UH50.. are equipped with an optical interface as standard. Also, up to 2 of the following communication modules can be used for remote readout:

Pulse module

WZU-P2

M-bus module

WZU-MB G4

M-bus module with 2 pulse inputs

WZU-MI

Analog module

WZU-AM

BACnet/Modbus module

WZU-485E-BAC, WZU-485E-MOD

RF module, 868 MHz

WZU-RF, WZU-RF-EXT

LoRaWAN module

WZU-LR, WZU-LR-EXT

NB IoT module

WZU-NB-IoT-G2

These modules have no impact on consumption metering and can therefore be replaced at any time without destroying the security seal.

Within 30 seconds after mounting (in case of the analog module up to 2 minutes), the meter automatically detects the module used and is then ready for communication or for delivering pulses.

The type of module used can be displayed within the service loop (loop 4) based on the display parameters.

Permissible module combinations

AM

Analog module

Step 1:

Slot for module 2 is equipped with...

MB G4

M-bus module

MB MI

M-bus module

RF

RF module

LoRa

LoRaWAN module

BACnet

BACnet module

Modbus

Modbus module

NB IoT

NB IoT module

 

 

AM (3)

Pulse module

MB G4

RF

LoRa

NB IoT

 

 

 

"Standard"

"Fast" (1)

 

 

 

 

Step 2:

Slot for module #1 can be equipped with...

AM

Yes

Yes

Yes

Yes

Yes

Yes

No

Pulse module (2) "Standard"

Yes

Yes

Yes

Yes

Yes

Yes

Yes

MB G4

Yes

Yes

Yes

Yes

Yes

Yes

Yes

MB MI

Yes

Yes

Yes

Yes

Yes

Yes

No

BACnet

No

No

No

Yes (4)

No

No

No

Modbus

No

No

No

Yes (4)

No

No

No

Restrictions:

* Only 1 module with fast pulses is possible; and only permissible in slot 2;

min. pulse duration:

  • 2 ms, if pulse module 1 is not fitted
  • 5 ms, if pulse module 1 is fitted

**) Subsequent mounting of a further pulse module in module slot 1 can result in changed output values for module 2!

(1) Pulse length of the fast pulses min. 5 ms

(2) The first and second channel can be configured individually!

(3) Do not insert the analog module in slot 2 on meters powered by AC 110/230 V

(4) Scan interval < 10 minutes requires D cell (6 years) or power supply.

Connection terminals

Multipin connection terminals are used to connect external cables to the modules.

Choice of connections

Solid or stranded wire

0.2…2.5 mm2

Stranded wire with ferrule

0.25…1.5 mm2

Cable sizes

26 – 14 AWG

 

Multiline connection (2 lines of same cross-sectional area)

Solid or stranded wire

0.2…0.75 mm2

Stranded wire with ferrule without plastic sleeve

0.25…0.34 mm2

Stranded wire with TWIN ferrule and plastic sleeve

0.5…0.75 mm2

Recommended screwdriver

0.6 x 3.5 mm

Tightening torque

0.4 Nm

 

The exterior diameter must be between 4 and 6 mm. All wiring must be able to be guided to the meter through the existing bushings. It may be convenient to connect the cables before the meter in a single multi-conductor cable on a split box.

Do not connect shielded cables on the meter side (connect to one end only).

Pulse module
WZU-P2

Function description

The pulse module WZU-P2 enables the meter to communicate with a pulse collector to transmit measured values. It outputs pulses that can be derived from the energy, volume, tariff register 1 or tariff register 2. Two channels are available; their function can be adapted using the service software.

The outputs are in the form of standard pulses or "fast pulses". The pulse duration is identical for channel 1 and channel 2.

The module can be plugged into either of the 2 slots. Fast pulses can only be supplied on slot 2.

Standard pulses

Standard pulse valencies

Continuous flow in m3/h

*) depending on the unit for heat energy display

Pulses for energy, volume, and tariff register

Period duration >200 ms

Pulse duration: 100 ms conducting

Pulse for operating states

"Ready"

Pulsed “conducting”, i.e. 0.1…0.25 ms pulse duration, 500 ms period

"Fault"

Constant "non-conducting"

Fast pulses

Applications, such as controllers or flow measuring sections, require higher pulse rates. The service software configures the parameters required for this purpose (pulse valency, pulse duration).

The maximum pulse frequency is 33 Hz.

NOTICE

Use a D cell for battery operation.

 

The following can be set:

  • Pulse type: "linear" or "scaled" pulses
  • Pulse output: Energy or volume
  • Pulse duration, if only 1 pulse module is fitted:
    • From 2 ms to 100 ms in increments of 1 ms
  • Pulse duration, if 2 pulse modules are fitted:
    • From 5 ms to 100 ms in increments of 5 ms

A suitable device can be used to receive and evaluate the pulses. Enter the settings in accordance with the controller’s data sheet.

Linear pulses are provided proportionally to the measured value. In the case of scaled pulses, the number of pulses at the upper and lower end of the range can be defined. In this case, the pulse receiving device can detect a wiring error, for example.

Linear pulses

Scaled pulses

Display on LCD

CE, C2, CV, CT or RI

Connection of outputs

(standard version):

M-bus module
WZU-MB G4
WZU-MI

Function description

The M-bus modules (WZU-MB G4 and WZU-MI) are used by the meter to communicate with an M-bus central unit to transmit measured values.

With the 2 M-bus modules, the secondary address is identical for both modules. It can be adjusted on the device using the module on slot 1 or via M-bus.

The data on the M-bus module is refreshed every 15 minutes.

A shorter sampling cycle can be set using the UltraAssist software.

The modules are available in 2 different versions:

WZU-MB G4

M-bus module for heat and heat/cooling energy meters, generation 4, recommended as of firmware 5.15 per EN 13757 and EN 1434-3.

WZU-MI

M-bus module with 2 pulse inputs for heat and heat/cooling energy meters, generation 4, recommended as of firmware 5.15 per EN 13757 and EN 1434-3.

Module WZU-MB G4 can be used in both slots. Always plug module WZU-MI into slot 1.

M-bus module with 2 pulse inputs
WZU-MI

Function description

In addition to the M-bus connection facility, the WZU-MI module has 2 pulse inputs to connect metering pulses from hot and cold water meters with Reed contact, relay or open collector. The cumulated volume is calculated based on the pulses and the set pulse valency, stored in the processor unit at 5-minute intervals and passed on via M-bus.

The volume values calculated by the meter from the pulse inputs cannot be officially calibrated.

In addition to possible power supply from the M-bus connection, the WZU-MI module is equipped with a battery. It powers the module processor and the pulse input, if no M-bus voltage is applied. Either isolated contacts (e.g. relay or Reed contacts) or electronic transmitters (open collectors) can be used as pulse transmitters for the pulse inputs. If an open collector circuit is used as the transmitter of the pulse inputs, the cable must always be electrically isolated from the M-bus inputs of the WZU-MI module.

BACnet/Modbus module
WZU-485E-BAC
WZU-485E-MOD

Both modules communicate with the processor via ModBus® or BACnetTM.

The ModBus® module is suitable (and preconfigured) for data transmission per the ModBus®-RTU protocol over RS485.

The BACnetTM module is suitable (and preconfigured) for data transmission per the BACnetTM protocol over RS485 and BACnetTM MS/TP.

NOTICE
Update internal memory

A value of  0 is returned if a data request arrives when the module is updating its internal memory.

  1. Set the data query to ≥15 s for data requests to the Modbus module (card).
  1. Set the data query to ≥15 s for broadcast command.

Mechanical design

WZU-485E-MOD

RTU communication over RS485, transmission rate up to 19200 baud, setting the transmission rate and parity of the software (USB, cable connection), refresh rate up to 10 sec. For UC50.. and for UH50.. as of firmware 5.15 and higher

WZU-485E-BAC

MS/TP communication over RS485, transmission rate up to 76800 baud, setting the transmission rate and parity of the software (USB, cable connection), refresh rate up to 10 sec. For UC50.. and for UH50.. as of firmware 5.15 and higher

Both modules are externally powered with AC/DC 24 V and galvanically isolated from the processor unit.

Switch off the module power supply before connecting it to the PC using the USB cable.

The micro USB interface is used exclusively to configure the communication protocol and speed.

Analog module
WZU-AM

Function description

The analog module (WZU-AM) converts the measured value from the meter to an analog signal. Each module has 2 channels with functions that can be configured independently. The service software configures the unit (selection of measured values and output ranges). The output signal is refreshed at 4-second intervals.

The analog module can be plugged into either of the 2 slots and 2 modules can be used concurrently.

Power supply

The module must be powered via an external power pack (e.g. WZU-NE24). The 2 cables of the power pack are interchangeable. The 2 analog modules can be powered by the same power pack.

The module(s) and the meter can be connected to the same power outlet if the meter is mains-powered (AC/DC 24 V). In this case, the wires must be bridged on module WZU-AM; the plug-in terminals on the meter’s power pack are not suited for that purpose.

If a meter is used with an analog module, a D-cell is required – if battery-powered.

External fuse

Each analog module must have its own external fuse.

RF module, 868 MHz
WZU-RF, WZU-RF-EXT

Function description

The RF modules (WZU-RF and WZU-RF-EXT) enable the meter to communicate wirelessly with a control unit at 868 MHz. They support data transmission conforming to OMS and DSMR. The meter time can be set when operating in conformance with DSMR. The maximum range is 400 meters.

NOTICE

Insert the module in slot 2.

The module is available in 2 different versions:

WZU-RF

Module with internal antenna

WZU-RF-EXT

Module with SMA, connection for external antenna

Data output conforming to OMS

The following data is available:

  • Current energy
  • Current volume
  • Present power
  • Current flow rate
  • Current temperatures heat and cold side
  • Error (manufacturer-specific)
  • Current time stamp (type I)

Other data telegrams are available on request (e.g. special telegrams for mobile data acquisition).

Power supply

The RF module is powered via the meter. A D-cell is required if the meter is battery powered.

LoRa module
WZU-LR / WZU-LR-EXT

Function description

The Long Range Wide Area Network (LoRaWAN) is a low-power network protocol. The LoRa alliance establishes the LoRaWAN specification; it is freely available and uses a special modulation technology.

The LoRaWAN module sends the meter data over a LoRaWAN wireless network to an application server (control unit) that the end customer can access. The meter data is transmitted immediately after start. The mobile ‘Elvaco OTC APP’ from Elvaco can configure the module.

Message type ‘Standard’ for the LoRa telegram includes the following data points:

  • Energy
  • Volume
  • Power
  • Flow rate
  • Flow temperature
  • Return temperature
  • Serial number
  • Error flag

At a transmission interval of 60 minutes, a battery life of 11 years can be achieved; at a transmission interval of 160 minutes, up to 16 years at good transmission quality.

NOTICE

Insert the module in slot 2.

NB IoT module
WZU-NB-IoT-G2

Function description

The NB IoT module sends the meter data over a NB IoT network to an application server (control unit) that the end customer can access. The meter data is transmitted immediately after start. The mobile ‘Elvaco OTC APP’ from Elvaco can configure the module.

The NB IoT telegram has the following data points:

  • Energy (kWh)
  • Volume(m3)
  • Power (kW)
  • Flow (m3/h)
  • Flow temperature (°C).
  • Return temperature (°C)
  • Serial number
  • Error flag
  • Data and time of meter reading

 

The module is displayed as 'MB G4'. The module is suitable for UH50.. meters as of firmware ≥5.15.

 

Meters equipped with the NB IoT module have optional antennas (WZU-ANT-WALL-MCX, WZU-ANT-MAG-MCX) and a battery (WZU-NB-IoT-BAT). A second battery (to the left of the battery compartment) is required (WZU-BC+GUM) if the meter is fully battery-operated. The module and meters can also be powered by just one power supply (24 V or 110/230 V).

Tariff control

The following options are available for tariff control.

The summation of energy and volume in the standard registers is performed independently of the tariff situation!

Threshold value tariff (tariffs T2, 3, 4, 5, 6)

Tariff registers 1, 2 and 3 can be controlled via up to 3 threshold values.

Either energy or volume can be added up in the tariff registers. The threshold values can be derived from the flow rate (tariff T2), power (tariff T3), temperature cold side (tariff T4), the flow temperature heat side (tariff T5), or the temperature differential (tariff T6).

Supplied energy / adjusted energy (tariff T7)

In tariff register 1, the energy calculated from the temperature heat side is totaled (and not from the temperature differential).

The 'Adjusted Energy' function (as of FW 5.24) adds the energy in tariff register 1 as calculated from the reference temperature and the temperature on the heat side.

Returned energy (tariff T8)

In tariff register 1, the energy calculated from the temperature cold side is totaled (and not from the temperature differential).

Heat/cooling energy meter (tariff T9)

In tariff register 1, the measured cooling energy is totaled; in tariff register 2, the measured heat energy. In both cases, a threshold can be defined via the temperature heat side (cold threshold, heat threshold).

Heat threshold exceeded and temperature difference > +0.2 K

=> The heat quantity is acquired

Cold threshold is breached and temperature differential < -0.2 K

=> Cooling energy is acquired

It is also measured in the event of negative temperature differentials.

Tariff control via time switch (tariff T10)

For tariff control, one switch-off time and one switch-on time per day can be defined. At the switch-on time, the energy or volume is totaled in tariff register 1 and ended at the switch-off time accordingly.

Tariff control via M-bus (tariff T11)

In tariff registers 1, 2 and 3, either energy or volume can be totaled. With the relevant M-bus command, one of the 3 tariffs can be activated or all tariffs can be deactivated.

Surcharge quantity tariff by means of return temperature (tariff T12)

The energy is totaled based on the temperature cold side in tariff registers 1 or 2.

The totaled energy is calculated from the temperature differential cold side and a defined return threshold (and not from the temperature differential).

Return threshold exceeded: T1 is totaled.

Return threshold breached: T2 is totaled.

Display of tariff situation on the LCD

The current tariff state is displayed in the user loop together with the energy or the volume in user LOOP 0.

No tariff state is displayed for tariffs T7 and T8.

 

For tariffs T2, T3, T4, T5, T6, T10, T11, and T12

No tariff register active

Tariff register 1 active

Tariff register 2 active

Tariff register 3 active

For tariff T9 (cooling energy/heat meter)

No tariff register active

Tariff register 1 active

Tariff register 2 active

The type of tariff and the associated parameters are displayed in service loop 4.

For T2, T3, T4, T5, and T6

At 2-second intervals with threshold value 1/2/3

For T7

For T8

For T9

At 2-second intervals

For T10

Switching times at 2-second intervals

For T11

For T12

The contents of the tariff registers is displayed in the user loop after the energy.

 

For tariffs T2, T3, T4, T5, T6, T10, T11, and T12

Tariff register 1

Tariff register 2

Tariff register 3 (not for T12)

For tariff T7

For tariff T8

For tariff T9

Log functions

In the internal logbook, measurement relevant events (errors, states, actions) are stored in chronological order with the time of occurrence. The acquired events are predefined. Logbook data cannot be deleted.

Each event is stored in a separate 4-level shift register; the overflows are transferred to a 25-level circulating buffer. So that at least the last 4 times can be traced for each event.

In a monthly register, the error states are stored for the current month and the past 18 months (without time stamp).

Serial no.

Description

1

F0 = Air in measuring tube

2

F1 = Interruption hot side temperature sensor

3

F2 = Interruption cold side temperature sensor

4

F3 = Error temperature electronics

5

F5 = Short circuit hot side temperature sensor

6

F6 = Short circuit cold side temperature sensor

7

F8 = Sensor error >8 hours

8

F9 = ASIC error

9

Above max. temperature in the flow measuring section

10

Below min. temperature in the flow measuring section

11

Max. flow rate qs exceeded

12

Soiling prewarning

13

Mains voltage off

14

CRC error occurred

15

Adjustment values parameterized

16

F7 (EEPROM) prewarning

17

Reset made

18

Date/time of day parameterized

19

Yearly set day parameterized

20

Monthly set day parameterized

21

Master reset performed

22

All times deleted

23

Error time was deleted

24

Maximum was deleted

The service software configures and reads out the data via the optical interface.

Data logger

The data logger (optional) permits archiving of data that the user can select from a predefined set of values. The data logger contains 4 archives to which 8 channels can be assigned. The data can be assigned to any of the channels. The service software is used for the configuration.

Archive

Time base

Storage depth

Averaging time for maximum

Hourly archive

1 hour

45 days

1 hour

Daily archive

1 day

65 days

1 hour

Monthly archive

1 month

15 months

1 hour

Yearly archive

1 year

15 years

1 hour/24 hours

*) For measuring periods of less than 1 hour, the highest value from the maximum values as calculated within 1 hour applies

The data is recorded with the values and time stamps. The service software configures and reads out the data via the optical interface.

Data transmission is in a manufacturer-specific format.

 

Value set for data to be recorded

Meter readings at the end of the period for...

Energy

Tariff register 1, 2, 3

Volume

Operating time *)

Fault duration *)

Pulse input 1

Pulse input 2

*) Depending on configuration: Hours or days

Instantaneous values at the end of the period for...

Power

Flow rate

Temperature heat side

Temperature cold side

Temperature difference

Indication of errors

Maximum for...

Power

Flow rate

Temperature heat side

Temperature cold side

Temperature difference