Metering accuracy as per EN 1434
The diagram below shows the typical metering accuracy of the UH50.., compared to the error limits per EN 1434, class 2.
Key:
EN 1434, class 3 | |
EN 1434, class 2 | |
UH50.. typical (EN 1434, ½ class 2) |
q | Current flow that determines the precision as a percentage of the continuous flow qp |
qi | Lower flow limit (value 1 on the x axis = 1 % of qp): |
qp | Continuous flow of meter = Value 100 on the x axis. |
The pressure loss in a flow sensor is indicated as continuous flow qp.
Actual pressure loss at the indicated flow can be calculated using the Kv value, which indicates flow at 1 bar differential pressure:
| Δp = Pressure loss in bar |
Q = Flow in m3 / h | |
Kv = Kv – Value at Δp = 1 bar |
Continuous flow qp m3/h | Mounting length mm | Connection | Pressure loss at qp mbar | Kv value at Δp = 1 bar m3/h | Curve in the diagram |
|---|---|---|---|---|---|
0.6 | 110, 190 | G ¾, G 1, DN20 | 150 | 1.5 | A |
1.5 | 130, 190 | G 1, DN20 | 160 | 3.8 | B |
1.5 | 110 | G ¾ | 150 | 3.9 | C |
2.5 | 190 | G 1, DN20 | 210 | 5.3 | D |
2.5 | 130 | G 1 | 200 | 5.6 | E |
3.5 | 260 | G 1¼, DN25 | 55 | 15 | G |
6 | 150 | G 1¼ | 190 | 14 | F |
6 | 260 | G 1¼, DN25 | 140 | 16 | H |
10 | 200, 300 | G 2, DN40 | 130 | 28 | I |
10 | 300 | G 2 | 110 | 30 | J |
15 | 270 | DN50 | 110 | 45 | K |
15 | 200 | DN50 | 95 | 49 | L |
25 | 300 | DN65 | 105 | 77 | M |
40 | 300 | DN80 | 160 | 100 | N |
60 | 360 | DN100 | 115 | 177 | O |
150 | 500 | DN150 | 120 | 433 | P |
The value can also be read graphically using the diagram as an alternative.
Pressure drop characteristic
Display
The meter displays current readings in kWh, MWh, MJ or GJ.
You can only select between kWh or MWh and MJ or GJ on the meter.
*) Decimal places "flashing", "static", or "suppressed"
The decimal places of displayed values are outlined to avoid errors.
Calibrated values are identified by a star symbol.
1 | Decimal places outlined | 2 | Calibrated value |
The number of decimal places of a value depends on the selected measuring path and the selected unit.
The meter’s displays are arranged in 5 loops:
- 1 user loop
- 4 service loops
1 | Display | 2 | Button 1 | ||
3 | Button 2 | 4 | Optical interface | ||
5 | Calibration seal |
|
| ||
A short press on button 1 enables selection of the required loop. The user loop reappears after the last loop. Press button 2 to read the value on the respective loop. The first value reappears after the last loop.
The range of display and the displayed data may deviate from this description and certain button functions may be disabled, depending on the parameter settings on the meter.
User loops
Detailed information on user loops is available under 'Product documentation’ data sheet CE2B5324.
Error codes
Detailed information on error codes is available under 'Product documentation’ data sheet M5324.
Standard parameters
It is programmed at the factory as follows:
- Set day [TT.MM]: 01.01
Power supply
The UH50.. can be powered by a power supply or battery.
Automatic mains detection
The power supply detects whether line voltage is present. The signal is provided to the UH50... The device automatically detects whether it is powered by a battery or a power supply.
Power packs
| |
Power pack AC/DC 24 V WZU-ACDC24-50 | Power pack AC 110/230 V WZU-AC110/230-15 WZU-AC110/230-50 |
Batteries
Standard battery (2 AA) WZU-BA+GUM | Universal battery with compartment for UN50.. And UC50.. WZU-BD-HALT |
| |
Battery with compartment for NB IoT module |
|
Battery life
Battery life depends on the type of battery and requirements
(e.g. short time base, analog module, etc.).
Install only batteries approved by the manufacturer.
Requirements (with time base Q = 4 s and T = 30 s) | 6 years | 11 years | 16 years | Power supply AC / DC 24 V |
Pulse module M-bus module G4 (Normal read mode 15 min.) BACnet/Modbus module (Read > 10 min.) | 2x AA | C | D | Yes |
RF module 868 MHz | D | D | D | Yes |
RF module 868 MHz | D | D | ‑ | Yes |
RF module LoRaWAN *) In Eco mode **) Powerpack: AC 110/230 V only | - | D *) | D *) | Yes **) |
RF module NB IoT-G2, band 3, 8, 20 | - | C ***) | - | Yes |
M-bus module G4 (Fast read mode 4 sec.) Pulse module (Fast pulses) Analog module BACnet/Modbus module (Read < 10 min.) | D | ‑ | ‑ | Yes |
Fast time base | D | ‑ | ‑ | Yes |
The following table displays the modules requiring an external power supply.
Module | Type of power supply |
|---|---|
|
BACnet/Modbus module | AC/DC 24 V, e.g. WZU-NE24 |
Analog module | AC/DC 24 V, e.g. WZU-NE24 |
Communication
Communication module
The communication modules are connected via a 6-pole reaction-free plug, enabling them to be installed or replaced at any time.
Compliance with ESD regulations must be ensured.
1 | Module 1 | 2 | Module 2 |
The UH50.. UH50.. are equipped with an optical interface as standard. Also, up to 2 of the following communication modules can be used for remote readout:
Pulse module | WZU-P2 |
M-bus module | WZU-MB G4 |
M-bus module with 2 pulse inputs | WZU-MI |
Analog module | WZU-AM |
BACnet/Modbus module | WZU-485E-BAC, WZU-485E-MOD |
RF module, 868 MHz | WZU-RF, WZU-RF-EXT |
LoRaWAN module | WZU-LR, WZU-LR-EXT |
NB IoT module | WZU-NB-IoT-G2 |
These modules have no impact on consumption metering and can therefore be replaced at any time without destroying the security seal.
Within 30 seconds after mounting (in case of the analog module up to 2 minutes), the meter automatically detects the module used and is then ready for communication or for delivering pulses.
The type of module used can be displayed within the service loop (loop 4) based on the display parameters.
Permissible module combinations
|
AM | Analog module | Step 1: Slot for module 2 is equipped with... | ||||||
MB G4 | M-bus module | |||||||
MB MI | M-bus module | |||||||
RF | RF module | |||||||
LoRa | LoRaWAN module | |||||||
BACnet | BACnet module | |||||||
Modbus | Modbus module | |||||||
NB IoT | NB IoT module | |||||||
|
| AM (3) | Pulse module | MB G4 | RF | LoRa | NB IoT | |
|
|
| "Standard" | "Fast" (1) |
|
|
|
|
Step 2: Slot for module #1 can be equipped with... | AM | Yes | Yes | Yes | Yes | Yes | Yes | No |
Pulse module (2) "Standard" | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |
MB G4 | Yes | Yes | Yes | Yes | Yes | Yes | Yes | |
MB MI | Yes | Yes | Yes | Yes | Yes | Yes | No | |
BACnet | No | No | No | Yes (4) | No | No | No | |
Modbus | No | No | No | Yes (4) | No | No | No | |
Restrictions:
* Only 1 module with fast pulses is possible; and only permissible in slot 2;
min. pulse duration:
- 2 ms, if pulse module 1 is not fitted
- 5 ms, if pulse module 1 is fitted
**) Subsequent mounting of a further pulse module in module slot 1 can result in changed output values for module 2!
(1) Pulse length of the fast pulses min. 5 ms
(2) The first and second channel can be configured individually!
(3) Do not insert the analog module in slot 2 on meters powered by AC 110/230 V
(4) Scan interval < 10 minutes requires D cell (6 years) or power supply.
Connection terminals
Multipin connection terminals are used to connect external cables to the modules.
Choice of connections | |
Solid or stranded wire | 0.2…2.5 mm2 |
Stranded wire with ferrule | 0.25…1.5 mm2 |
Cable sizes | 26 – 14 AWG |
Multiline connection (2 lines of same cross-sectional area) | |
Solid or stranded wire | 0.2…0.75 mm2 |
Stranded wire with ferrule without plastic sleeve | 0.25…0.34 mm2 |
Stranded wire with TWIN ferrule and plastic sleeve | 0.5…0.75 mm2 |
Recommended screwdriver | 0.6 x 3.5 mm |
Tightening torque | 0.4 Nm |
The exterior diameter must be between 4 and 6 mm. All wiring must be able to be guided to the meter through the existing bushings. It may be convenient to connect the cables before the meter in a single multi-conductor cable on a split box.
Do not connect shielded cables on the meter side (connect to one end only).
Pulse module
WZU-P2
Function description
The pulse module WZU-P2 enables the meter to communicate with a pulse collector to transmit measured values. It outputs pulses that can be derived from the energy, volume, tariff register 1 or tariff register 2. Two channels are available; their function can be adapted using the service software.
The outputs are in the form of standard pulses or "fast pulses". The pulse duration is identical for channel 1 and channel 2.
The module can be plugged into either of the 2 slots. Fast pulses can only be supplied on slot 2.
Standard pulses
Standard pulse valencies
Continuous flow in m3/h
*) depending on the unit for heat energy display
Pulses for energy, volume, and tariff register
Period duration >200 ms Pulse duration: 100 ms conducting |
Pulse for operating states
"Ready" | Pulsed “conducting”, i.e. 0.1…0.25 ms pulse duration, 500 ms period |
"Fault" | Constant "non-conducting" |
Fast pulses
Applications, such as controllers or flow measuring sections, require higher pulse rates. The service software configures the parameters required for this purpose (pulse valency, pulse duration).
The maximum pulse frequency is 33 Hz.
Use a D cell for battery operation.
The following can be set:
- Pulse type: "linear" or "scaled" pulses
- Pulse output: Energy or volume
- Pulse duration, if only 1 pulse module is fitted:
- From 2 ms to 100 ms in increments of 1 ms
- Pulse duration, if 2 pulse modules are fitted:
- From 5 ms to 100 ms in increments of 5 ms
A suitable device can be used to receive and evaluate the pulses. Enter the settings in accordance with the controller’s data sheet.
Linear pulses are provided proportionally to the measured value. In the case of scaled pulses, the number of pulses at the upper and lower end of the range can be defined. In this case, the pulse receiving device can detect a wiring error, for example.
Linear pulses | Scaled pulses |
Display on LCD | CE, C2, CV, CT or RI |
Connection of outputs (standard version): |
M-bus module
WZU-MB G4
WZU-MI
Function description
The M-bus modules (WZU-MB G4 and WZU-MI) are used by the meter to communicate with an M-bus central unit to transmit measured values.
With the 2 M-bus modules, the secondary address is identical for both modules. It can be adjusted on the device using the module on slot 1 or via M-bus.
The data on the M-bus module is refreshed every 15 minutes.
A shorter sampling cycle can be set using the UltraAssist software.
The modules are available in 2 different versions:
WZU-MB G4 | M-bus module for heat and heat/cooling energy meters, generation 4, recommended as of firmware 5.15 per EN 13757 and EN 1434-3. |
WZU-MI | M-bus module with 2 pulse inputs for heat and heat/cooling energy meters, generation 4, recommended as of firmware 5.15 per EN 13757 and EN 1434-3. |
Module WZU-MB G4 can be used in both slots. Always plug module WZU-MI into slot 1.
M-bus module with 2 pulse inputs
WZU-MI
Function description
In addition to the M-bus connection facility, the WZU-MI module has 2 pulse inputs to connect metering pulses from hot and cold water meters with Reed contact, relay or open collector. The cumulated volume is calculated based on the pulses and the set pulse valency, stored in the processor unit at 5-minute intervals and passed on via M-bus.
The volume values calculated by the meter from the pulse inputs cannot be officially calibrated.
In addition to possible power supply from the M-bus connection, the WZU-MI module is equipped with a battery. It powers the module processor and the pulse input, if no M-bus voltage is applied. Either isolated contacts (e.g. relay or Reed contacts) or electronic transmitters (open collectors) can be used as pulse transmitters for the pulse inputs. If an open collector circuit is used as the transmitter of the pulse inputs, the cable must always be electrically isolated from the M-bus inputs of the WZU-MI module.
BACnet/Modbus module
WZU-485E-BAC
WZU-485E-MOD
Both modules communicate with the processor via ModBus® or BACnetTM.
The ModBus® module is suitable (and preconfigured) for data transmission per the ModBus®-RTU protocol over RS485.
The BACnetTM module is suitable (and preconfigured) for data transmission per the BACnetTM protocol over RS485 and BACnetTM MS/TP.
A value of 0 is returned if a data request arrives when the module is updating its internal memory.
- Set the data query to ≥15 s for data requests to the Modbus module (card).
- Set the data query to ≥15 s for broadcast command.
Mechanical design
WZU-485E-MOD | RTU communication over RS485, transmission rate up to 19200 baud, setting the transmission rate and parity of the software (USB, cable connection), refresh rate up to 10 sec. For UC50.. and for UH50.. as of firmware 5.15 and higher |
WZU-485E-BAC | MS/TP communication over RS485, transmission rate up to 76800 baud, setting the transmission rate and parity of the software (USB, cable connection), refresh rate up to 10 sec. For UC50.. and for UH50.. as of firmware 5.15 and higher |
Both modules are externally powered with AC/DC 24 V and galvanically isolated from the processor unit.
Switch off the module power supply before connecting it to the PC using the USB cable.
The micro USB interface is used exclusively to configure the communication protocol and speed.
Analog module
WZU-AM
Function description
The analog module (WZU-AM) converts the measured value from the meter to an analog signal. Each module has 2 channels with functions that can be configured independently. The service software configures the unit (selection of measured values and output ranges). The output signal is refreshed at 4-second intervals.
The analog module can be plugged into either of the 2 slots and 2 modules can be used concurrently.
Power supply
The module must be powered via an external power pack (e.g. WZU-NE24). The 2 cables of the power pack are interchangeable. The 2 analog modules can be powered by the same power pack.
The module(s) and the meter can be connected to the same power outlet if the meter is mains-powered (AC/DC 24 V). In this case, the wires must be bridged on module WZU-AM; the plug-in terminals on the meter’s power pack are not suited for that purpose.
If a meter is used with an analog module, a D-cell is required – if battery-powered.
External fuse
Each analog module must have its own external fuse.
RF module, 868 MHz
WZU-RF, WZU-RF-EXT
Function description
The RF modules (WZU-RF and WZU-RF-EXT) enable the meter to communicate wirelessly with a control unit at 868 MHz. They support data transmission conforming to OMS and DSMR. The meter time can be set when operating in conformance with DSMR. The maximum range is 400 meters.
Insert the module in slot 2.
The module is available in 2 different versions:
WZU-RF | Module with internal antenna |
WZU-RF-EXT | Module with SMA, connection for external antenna |
Data output conforming to OMS
The following data is available:
- Current energy
- Current volume
- Present power
- Current flow rate
- Current temperatures heat and cold side
- Error (manufacturer-specific)
- Current time stamp (type I)
Other data telegrams are available on request (e.g. special telegrams for mobile data acquisition).
Power supply
The RF module is powered via the meter. A D-cell is required if the meter is battery powered.
LoRa module
WZU-LR / WZU-LR-EXT
Function description
The Long Range Wide Area Network (LoRaWAN) is a low-power network protocol. The LoRa alliance establishes the LoRaWAN specification; it is freely available and uses a special modulation technology.
The LoRaWAN module sends the meter data over a LoRaWAN wireless network to an application server (control unit) that the end customer can access. The meter data is transmitted immediately after start. The mobile ‘Elvaco OTC APP’ from Elvaco can configure the module.
Message type ‘Standard’ for the LoRa telegram includes the following data points:
- Energy
- Volume
- Power
- Flow rate
- Flow temperature
- Return temperature
- Serial number
- Error flag
At a transmission interval of 60 minutes, a battery life of 11 years can be achieved; at a transmission interval of 160 minutes, up to 16 years at good transmission quality.
Insert the module in slot 2.
NB IoT module
WZU-NB-IoT-G2
Function description
The NB IoT module sends the meter data over a NB IoT network to an application server (control unit) that the end customer can access. The meter data is transmitted immediately after start. The mobile ‘Elvaco OTC APP’ from Elvaco can configure the module.
The NB IoT telegram has the following data points:
- Energy (kWh)
- Volume(m3)
- Power (kW)
- Flow (m3/h)
- Flow temperature (°C).
- Return temperature (°C)
- Serial number
- Error flag
- Data and time of meter reading
The module is displayed as 'MB G4'. The module is suitable for UH50.. meters as of firmware ≥5.15.
Meters equipped with the NB IoT module have optional antennas (WZU-ANT-WALL-MCX, WZU-ANT-MAG-MCX) and a battery (WZU-NB-IoT-BAT). A second battery (to the left of the battery compartment) is required (WZU-BC+GUM) if the meter is fully battery-operated. The module and meters can also be powered by just one power supply (24 V or 110/230 V).
Tariff control
The following options are available for tariff control.
The summation of energy and volume in the standard registers is performed independently of the tariff situation!
Threshold value tariff (tariffs T2, 3, 4, 5, 6)
Tariff registers 1, 2 and 3 can be controlled via up to 3 threshold values.
Either energy or volume can be added up in the tariff registers. The threshold values can be derived from the flow rate (tariff T2), power (tariff T3), temperature cold side (tariff T4), the flow temperature heat side (tariff T5), or the temperature differential (tariff T6).
Supplied energy / adjusted energy (tariff T7)
In tariff register 1, the energy calculated from the temperature heat side is totaled (and not from the temperature differential).
The 'Adjusted Energy' function (as of FW 5.24) adds the energy in tariff register 1 as calculated from the reference temperature and the temperature on the heat side.
Returned energy (tariff T8)
In tariff register 1, the energy calculated from the temperature cold side is totaled (and not from the temperature differential).
Heat/cooling energy meter (tariff T9)
In tariff register 1, the measured cooling energy is totaled; in tariff register 2, the measured heat energy. In both cases, a threshold can be defined via the temperature heat side (cold threshold, heat threshold).
Heat threshold exceeded and temperature difference > +0.2 K
=> The heat quantity is acquired
Cold threshold is breached and temperature differential < -0.2 K
=> Cooling energy is acquired
It is also measured in the event of negative temperature differentials.
Tariff control via time switch (tariff T10)
For tariff control, one switch-off time and one switch-on time per day can be defined. At the switch-on time, the energy or volume is totaled in tariff register 1 and ended at the switch-off time accordingly.
Tariff control via M-bus (tariff T11)
In tariff registers 1, 2 and 3, either energy or volume can be totaled. With the relevant M-bus command, one of the 3 tariffs can be activated or all tariffs can be deactivated.
Surcharge quantity tariff by means of return temperature (tariff T12)
The energy is totaled based on the temperature cold side in tariff registers 1 or 2.
The totaled energy is calculated from the temperature differential cold side and a defined return threshold (and not from the temperature differential).
Return threshold exceeded: T1 is totaled.
Return threshold breached: T2 is totaled.
Display of tariff situation on the LCD
The current tariff state is displayed in the user loop together with the energy or the volume in user LOOP 0.
No tariff state is displayed for tariffs T7 and T8.
For tariffs T2, T3, T4, T5, T6, T10, T11, and T12
No tariff register active | |
Tariff register 1 active | |
Tariff register 2 active | |
Tariff register 3 active |
For tariff T9 (cooling energy/heat meter)
No tariff register active | |
Tariff register 1 active | |
Tariff register 2 active |
The type of tariff and the associated parameters are displayed in service loop 4.
For T2, T3, T4, T5, and T6 | |
At 2-second intervals with threshold value 1/2/3 | |
For T7 | |
For T8 | |
For T9 | |
At 2-second intervals | |
For T10 | |
Switching times at 2-second intervals | |
For T11 | |
For T12 |
The contents of the tariff registers is displayed in the user loop after the energy.
For tariffs T2, T3, T4, T5, T6, T10, T11, and T12
Tariff register 1 | |
Tariff register 2 | |
Tariff register 3 (not for T12) | |
For tariff T7 | |
For tariff T8 | |
For tariff T9 |
Log functions
In the internal logbook, measurement relevant events (errors, states, actions) are stored in chronological order with the time of occurrence. The acquired events are predefined. Logbook data cannot be deleted.
Each event is stored in a separate 4-level shift register; the overflows are transferred to a 25-level circulating buffer. So that at least the last 4 times can be traced for each event.
In a monthly register, the error states are stored for the current month and the past 18 months (without time stamp).
Serial no. | Description |
|---|---|
|
1 | F0 = Air in measuring tube |
2 | F1 = Interruption hot side temperature sensor |
3 | F2 = Interruption cold side temperature sensor |
4 | F3 = Error temperature electronics |
5 | F5 = Short circuit hot side temperature sensor |
6 | F6 = Short circuit cold side temperature sensor |
7 | F8 = Sensor error >8 hours |
8 | F9 = ASIC error |
9 | Above max. temperature in the flow measuring section |
10 | Below min. temperature in the flow measuring section |
11 | Max. flow rate qs exceeded |
12 | Soiling prewarning |
13 | Mains voltage off |
14 | CRC error occurred |
15 | Adjustment values parameterized |
16 | F7 (EEPROM) prewarning |
17 | Reset made |
18 | Date/time of day parameterized |
19 | Yearly set day parameterized |
20 | Monthly set day parameterized |
21 | Master reset performed |
22 | All times deleted |
23 | Error time was deleted |
24 | Maximum was deleted |
The service software configures and reads out the data via the optical interface.
Data logger
The data logger (optional) permits archiving of data that the user can select from a predefined set of values. The data logger contains 4 archives to which 8 channels can be assigned. The data can be assigned to any of the channels. The service software is used for the configuration.
|
Archive | Time base | Storage depth | Averaging time for maximum |
Hourly archive | 1 hour | 45 days | 1 hour |
Daily archive | 1 day | 65 days | 1 hour |
Monthly archive | 1 month | 15 months | 1 hour |
Yearly archive | 1 year | 15 years | 1 hour/24 hours |
*) For measuring periods of less than 1 hour, the highest value from the maximum values as calculated within 1 hour applies
The data is recorded with the values and time stamps. The service software configures and reads out the data via the optical interface.
Data transmission is in a manufacturer-specific format.
| Value set for data to be recorded |
|---|---|
Meter readings at the end of the period for... | Energy Tariff register 1, 2, 3 Volume Operating time *) Fault duration *) Pulse input 1 Pulse input 2 *) Depending on configuration: Hours or days |
Instantaneous values at the end of the period for... | Power Flow rate Temperature heat side Temperature cold side Temperature difference Indication of errors |
Maximum for... | Power Flow rate Temperature heat side Temperature cold side Temperature difference |