2-pipe fan coil unit - Basic Documentation - RDF600KN/VB - RDF600KN - RDF600KN/S

Semi-flush mount room thermostats with KNX communications RDF301, RDF301.50, RDF301.50H, RDF600KN, RDF600KN/VB, RDF600KN/S

Product Family
Desigo Open
Desigo PX Open
Product Group
Thermostats (temperature controller with sensor)
Building automation
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2020-02-21
Document No
CE1P3171en
Download ID
A6V10385333
Stock No.
S55770-T400
S55770-T430
S55770-T293
Product No.
RDF600KN/VB
RDF600KN
RDF600KN/S
Access level
Internet
File Type
html
md

On 2-pipe applications, the thermostat controls a valve in heating / cooling mode with changeover (automatically or manually), heating only, or cooling only. Cooling only is factory-set (P01 = 1).

ON/OFF control

Control sequence
ON/OFF output

The diagrams below show the control sequence for 2-position control.

Heating mode Cooling mode
T[°C] Room temperature SDH Switching differential "Heating" (P30)
w Room temperature setpoint SDC Switching differential "Cooling" (P31)
Y1 Control command "Valve" or "Compressor"

Modulating control: 3-position

Control sequence modulating output

The diagrams below show the control sequence for modulating PI control.

Heating mode Cooling mode
T[°C] Room temperature XpH Proportional band "Heating" (P30)
w Room temperature setpoint XpC Proportional band "Cooling" (P31)
Y1 Control command "Valve"

Notes:

  • The diagrams only show the PI thermostat’s proportional part.

  • For the fan sequence see section 3.8.

Setting the sequence and the control outputs

Refer to section 3.4 Applications overview, section 3.6.1 Sequences overview (setting via parameter P01) and section 3.7 Control outputs.