Parameter setting via local HMI - Basic Documentation - RDF600KN/VB - RDF600KN - RDF600KN/S

Semi-flush mount room thermostats with KNX communications RDF301, RDF301.50, RDF301.50H, RDF600KN, RDF600KN/VB, RDF600KN/S

Product Family
Desigo Open
Desigo PX Open
Product Group
Thermostats (temperature controller with sensor)
Building automation
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2020-02-21
Document No
CE1P3171en
Download ID
A6V10385333
Stock No.
S55770-T400
S55770-T430
S55770-T293
Product No.
RDF600KN/VB
RDF600KN
RDF600KN/S
Access level
Internet
File Type
html
md

Enter only "Service" level

1. Press buttons + and – simultaneously for 4 seconds.
Release and press button + again within 2 seconds until the display shows "P01".
Continue with step 2.

Enter "Service" and "Expert" level.

1. Press buttons + and – simultaneously for 4 seconds.
Release and press button – again within 2 seconds until the display shows "P01".

Adjust parameters

2. Repeatedly press the + or button to select the required parameter.

3. Press + and simultaneously. The current value of the selected parameter begins to flash, allowing you to change the value by repeatedly pressing + or .

4. The next parameter is displayed when you press + and again simultaneously.

5. Repeat steps 2 to 4 to display and change additional parameters.

6. Press + or – until "End" is displayed, and then press + and – simultaneously to save the change and exit parameter entry mode.

Reset parameters

The factory setting for the control parameters can be reloaded via parameter P71, by changing the value to "ON", and confirming by pressing buttons + and simultaneously. The display shows "8888" during reload.