For compressor applications,

  • set the corresponding basic application

  • disable the fan (P52) or set the fan speed (P53)

The following applications are available:

Application for compressor Set basic application See section Sequences
1-stage compressor
for heating or cooling
2-pipe 3.6.3

H ( \ )

C ( / )

1-stage compressor and electric heater

(for cooling only: disable electric heater via P13)

2-pipe and electric heater 3.6.4

El H + H ( ⭍\ \ )

El H + C ( ⭍\ / )

C ( / )

1-stage compressor
for heating and cooling
4-pipe 3.6.5 H + C ( \ / )

Note:

  • Minimum ON/OFF time: P48 / P49

  • Fan operation:P52 (0 = disabled, 1 = enabled)

  • Fan speed: P53 (1 = 1-speed, 2 = 3-speed)