Chilled / heated ceiling and radiator applications* - Basic Documentation - RDF600KN/VB - RDF600KN - RDF600KN/S

Semi-flush mount room thermostats with KNX communications RDF301, RDF301.50, RDF301.50H, RDF600KN, RDF600KN/VB, RDF600KN/S

Product Family
Desigo Open
Desigo PX Open
Product Group
Thermostats (temperature controller with sensor)
Building automation
Content Language
English
Content Type
Technical Documentation > Basic Documentation
Product Version
Status
Valid
Date
2020-02-21
Document No
CE1P3171en
Download ID
A6V10385333
Stock No.
S55770-T400
S55770-T430
S55770-T293
Product No.
RDF600KN/VB
RDF600KN
RDF600KN/S
Access level
Internet
File Type
html

For chilled / heated ceiling and radiator,

  • set the corresponding basic application

  • disable the fan (P52)

The following applications are available:

Application for
chilled / heated ceiling, radiator
Set basic application See section Sequences
Chilled / heated ceiling with changeover 2-pipe 3.6.3

H ( \ )

C ( / )

Chilled / heated ceiling & el heater

(cooling only: disable el heater via P13)

2-pipe and electric heater 3.6.4

El H + H ( ⭍\ \ )

El H + C ( ⭍\ / )

C ( / )

Chilled ceiling and radiator 4-pipe 3.6.5 H + C ( \ / )

* Not applicable for RDF301 and RDF301.50.