Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

 

Syntax

If (pt1.eq.DAYMOD) then...

pt1

A point name whose operational status is compared to the status indicator.
Use the equipment controller application name.

- For APOGEE firmware, use the TEC application name.

- For pre-APOGEE firmware, define the point as an LCTLR point type

Use

This status indicator determines if an equipment controller is in DAY mode.

For some equipment controllers, DAY mode is also referred to as OCC (occupied) mode. If an equipment controller is in occupied mode, PPCL recognizes this status as DAYMOD.

Example

200  IF (CTLR1.EQ.DAYMOD) THEN DAYSP = 75.0

Notes

This command is only valid for FLN controllers and is not recommended for use with PXC.A firmware.

  • For BACnet firmware, the application name corresponds to PTECs and DXR2s.
  • For APOGEE firmware, the application name can correspond to a TEC, LTEC, or UC.
  • For pre-APOGEE firmware, LCTLR and LTCU point types must be used.