If (pt1.eq ALMACK) then...

pt1

A point name that is alarmable.

Use

This status indicator determines the status of an alarm acknowledgement. This comparison is true if the point alarm state has been acknowledged.

Example 1

In the following statement, FAN is an alarmable point with Normal Acknowledge Required by Operator Enabled.

200  IF (FAN.EQ.ALMACK) THEN ON(PT1) ELSE OFF(PT1)

Action

System Response

FAN is commanded ON

Alarm

Alarm state is acknowledged

pt1 turns ON

FAN is commanded OFF

pt1 turns OFF (Fan is OFF and Normal, but requires acknowledgement)

FAN Return to Normal state is acknowledged

p1 turns ON

Example 2

In the following statement, FAN is an alarmable point with Normal Acknowledge Required by Operator Disabled.

200 IF (TEMP02.EQ.ALARM) THEN ON(FAN)

Action

System Response

FAN is commanded ON

Alarm

Alarm state is acknowledged

pt1 turns ON

FAN is commanded OFF

pt1 remains ON (Fan is OFF and Normal. The Return to Normal has been acknowledged internally.)

Notes

For BACnet firmware, the ALMACK is true if any alarm event has been acknowledged; that is, OFFNORMAL, NORMAL, or FAULT