The following statements are not supported in PXC.A devices. The PXC.A PPCL runtime will consider these statements to be invalid, and no replacements are provided.

Statement(s) Removed

Notes

ADAPTM (Adaptive control, multiple)
ADAPTS (Adaptive control, single)

The ADAPT application is not supported in PXC.A devices.

DISCOV (Disable COV Reporting)
ENCOV (Enable COV Reporting)

Programmatic COV enable/disable is not supported in PXC.A devices.

DPHONE (Disable phone)
EPHONE (Enable phone)

Dialup modems are not supported in PXC.A devices.

OIP (Operator interface program)

The PRMMI, along with its menu prompt tree, is not supported in PXC.A devices. Based on need, limited alternative to the OIP statement may be provided in a future product release.

ONPWRT (On after power return)

PXC.A devices do not have warmstart functionality, therefore a PPCL program will always start at the first line after a power failure.

ALARM (Command to alarm state)
NORMAL (Command to normal state)

Commanding into and out of alarm state is not supported in PXC.A devices.