Unitary | Pre-APOGEE | APOGEE | BACnet | PXC.A |
---|---|---|---|---|
● | ● | ● | ● | ● |
Syntax
SAMPLE(sec) line
sec | Interval in seconds between evaluations of state. - This value must be entered as an integer ranging from 1 to 32,767. |
line | Any PPCL statement that does not include its own timing function. This includes: |
Use
Defines how often a command is evaluated. The SAMPLE command can be helpful in situations, such as preventing short cycling in ON/OFF decisions or reducing COVs from noisy flow transmitters.
Example
200 SAMPLE(600) ON(HALFAN)
Notes
The SAMPLE command executes immediately on a return from power failure, after an ENABLE command, or during the first execution of PPCL following a database load.
Valid commands can include assignment, calculations, and program control (GOTO, GOSUB).