Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

Syntax

LOCAL(pt1,... ,pt16)

Use

Creates virtual points for the program.

  • The program can reference these points as $pt1 through $pt16.
  • Other programs can reference these points by referencing the program name, followed by the system delimiter (:), followed by the local point name.
  • For PXC.A controllers, these points can only be accessed from within the device.
  • For PXC.A controllers, there is no limit to the number of local objects that can be generated.

Example 1

The following is an example of commanding a local point contained within a program:

10  IF (FANRUN.GE.1000) THEN GOTO 50

Example 2

The following is an example of a program using the value of a local point in a different program (where PROG1 is the program name):

300  IF(“PROG1:FANPT”.EQ.ON)THEN ...