Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

Syntax

INITTO(value,pt1,...,pt15)

value

The new value which replaces the current totalized values for all specified points.

-  This value can be a decimal, point name, or local variable. Integers are not allowed.

pt1 through pt15

Names of points that are defined for totalization. Points must reside in the same device as the control program

Use

Change the totalized value of a point to a new value (generally 0).

A maximum of 15 point names can receive the new value through one INITTO command.

Example

10  IF (DAYOFM.EQ.1.0) THEN INITTO(0.0, PMP1,PMP2)

Notes

  • Points must reside in the same device as the command.
  • The INITTO command cannot reset the value of LPACI point types.
  • Only points that are defined to be totalized can be initialized by this command.
  • When used in APOGEE automation stations (which can totalize individual states of a point), INITTO will reset all totalized states of a digital point to zero.