Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

Syntax

EPHONE(pn#1,...,pn#16)

pn#1 through pn#16

Telephone ID numbers that are defined in the device.

Use

This statement is no longer supported in PXC.A devices. The PXC.A PPCL runtime will consider this statement invalid, and no replacements have been provided.

Enables telephone ID numbers. The telephone ID number is a numeric code that represents the actual telephone number defined in the device.

A maximum of 16 telephone number IDs can be enabled with one EPHONE command.

Example

530  EPHONE(1,2,3,5,6)

Notes

Do not use the EPHONE command over the network.

See also the DPHONE topic.