Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

 

Syntax

EMON(pt1,...,pt16)

pt1 through pt16

Point name to be set to ON status with emergency priority.

- This parameter can be a LDI, LDO, L2SL, L2SP, LOOAL, or LOOAP point.

Use

For PXC.A devices, this statement has been replaced with SET (Set point value).

Changes the operational status of the specified points to ON with emergency priority.

A maximum of 16 points can be changed with one EMON command.

See also the EMAUTO, EMFAST, EMOFF, EMSET, and EMSLOW topics.