Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

 

Syntax

EMOFF(pt1,...,pt16)

pt1 through pt16

Point name to be set to OFF status with emergency priority.

- This parameter can be a LDI, LDO, LFSSL, LFSSP, LOOAL, LOOAP, L2SL, or L2SP point.

Use

For PXC.A devices, this statement has been replaced with SET (Set point value).

Changes the operational status of the specified points to OFF with emergency priority.

A maximum of 16 points can be changed with one EMOFF command.

See also the EMAUTO, EMFAST, EMON, EMSET, and EMSLOW topics.