Unitary | Pre-APOGEE | APOGEE | BACnet | PXC.A |
---|---|---|---|---|
| ● | ● | ● | ● |
Syntax
EMAUTO(pt1,...,pt16)
pt1 through pt16 | Point name to be set to AUTO status with emergency priority. - This parameter can be a LOOAL or LOOAP point. |
Use
For PXC.A devices, this statement has been replaced with SET (Set point value).
Changes the operational status of an ON/OFF/AUTO point to AUTO (local control) with emergency priority.