Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

 

Syntax

AUTO(line1,...,line16)

line1 through line16

Name of a point to be set to AUTO status.

- This parameter must be a LOOAL or LOOAP point type.

Use

For PXC.A devices, this statement has been replaced with SET (Set point value).

Changes the operational status of an ON/OFF/AUTO point to AUTO.

A maximum of 16 points can be changed with one AUTO command.

Example

100  AUTO(EFAN1,EFAN2,EFAN3)

See also the FAST, OFF, ON, and SLOW topics.