The second option allows you to release points at a specific priority to the NONE priority. In the following example, any of the points included in the RELEAS command that have a priority of EMER or lower, will be released to the NONE priority:

300  RELEAS(@EMER,FAN1,FAN2)

Note that if the point specified is at an equal or lower priority than EMER, it will also be released to NONE. In other words:

If the point specified is at this priority…

Using this pre‑APOGEE command…

Changes the priority to…

OPER

RELEAS(@OPER … )

NONE

SMOKE

 

NONE

EMER

 

NONE

PDL

 

NONE

OPER

RELEAS(@SMOKE … )

or

RELEASE(@EMER … )

OPER

SMOKE

 

NONE

EMER

 

NONE

PDL

 

NONE

OPER

RELEAS(@PDL … )

OPER

SMOKE

 

SMOKE

EMER

 

EMER

PDL

 

NONE

For a complete description of the RELEAS command, see the RELEAS topic.