Section 1
Compatibility Bar

 

Section 2
Syntax

Syntax

DISALM(pt1,...,pt16)

pt1 through pt16

Names of the points that should have alarm reporting disabled.

Section 3
Use

Use

This command disables the alarm printing capabilities for specified points. Up to 16 points can be enabled for alarm reporting by one command. The point status changes to *PDSB* after it has been DISALMed.

Example

50 IF (SFAN.EQ.OFF) THEN DISALM(ROOM1) ELSE

ENALM(ROOM1)

Section 4
Notes
(If Applicable)

Notes

This command cannot be used for points that do not reside in the device in which the control program is written. DISALM cannot be used to directly disable alarm reporting over the network.

Section 5
See Also
(If Applicable)

See also

ALARM, ENALM, HLIMIT, LLIMIT, NORMAL