The following example illustrates the results when defining holidays using the PPCL HOLIDA command.

50  HOLIDA(5,3,9,8)

The following TOD commands are defined in the TOD database:

Monday - Sunday

07:00:00

OFF

LITE1

18:00:00

ON

FAN1

18:00:00

ON

LITE1

19:00:00

OFF

FAN1

Holiday

10:30:00

OFF

LITE1

17:00:00

ON

LITE1

Based on this schedule, the following will occur:

  • Every day except May 3 and September 8, LITE1 will go ON at 18:00 and turn OFF at 07:00, and FAN1 will go ON at 18:00 and turn OFF at 19:00.
  • On May 3 and September 8, LITE1 will go ON at 17:00 and turn OFF at 10:30, while FAN1 will not be commanded.