PXC.A

Syntax

SECNDn

n

The number that describes which SECNDn point is referenced.

- Valid values for SECNDn are 1 through 7.

Use

These seven resident points count real time seconds and can be used as timers. The computer adds one (1) to the SECNDn variable for every one second of real time that passes.

  • The value of a SECNDn point can only be set by a PPCL command.
  • The maximum value a SECNDn point can be set to is 9,999.

Example

600  IF(SECND1.GT.15) THEN ON(RF) ELSE OFF(RF)

Notes

For APOGEE automation stations, each program has unique SECNDSn points. These points can also be viewed in the interface using the program name, system delimiter (:)SECNDSn format.