Unitary | Pre-APOGEE | APOGEE | BACnet | PXC.A |
---|---|---|---|---|
● | ● | ● | ● | ● |
Syntax
DAY
Use
This resident point specifies the current day of the week. The values used for the DAY point are as follows:
Number | Day of the Week |
---|---|
1 | Monday |
2 | Tuesday |
3 | Wednesday |
4 | Thursday |
5 | Friday |
6 | Saturday |
7 | Sunday |
Example
300 IF (DAY.EQ.1) THEN TOTRAN = 0
Notes
These values are not related to the modes used in the TODMOD statement.