Unitary

Pre-APOGEE

APOGEE

BACnet

PXC.A

Syntax

pt1 = (value1)

pt1

The point name or local variable that receives the value from value1.

value1

A point name, local variable, expression, or number that is assigned to pt1.

Use

Assigns the value of value1 to the value of pt1.

Example

COUNT = COUNT + 1.0

Notes

Do not to assign values to reserved words. See the Appendix A - Reserved Word List.

Example

500  C = OATEMP

The code in this example would fail due to the “C” being used like a variable, when instead the automation station interprets the line as a comment.