To update the firmware on an FCA2015-U1 that is installed on a XLS/Desigo Fire Safety Modular/Cerberus PRO Modular system, establish an Ethernet connection between the PC and the OI, then select the XDACT module in the Zeus configuration. Next, select Build > Transfer > Module Firmware To Panel… in Zeus. Select the XDACT firmware file under Firmware File, then set the Connection Settings as needed and click Start Transfer to begin the update. Transfer Completed will be displayed in Zeus after the firmware update has completed.