Dialer FCA2015-U1 mounted on 2HU Enclosure

Steps:

  1. Installation should be performed by qualified personnel who have thoroughly read and understood this instruction sheet.
  2. Disconnect BATTERY and AC on the cabinet prior to working on the equipment.
  3. Mount FCA2015-U1 as shown using the four screws that are supplied.
  4. Attach conduit and run wires as required. Wire Size: 12-22AWG
  5. Connect the Serial Communication Cable to the fire system control unit as required.
  6. Apply power to system.
  7. Program for proper operation.
  8. See the Desigo FC2025/2050, FV2025/2050 Configuration manual, Document ID A6V10315023, and Cerberus PRO FC922/924, FV922/924 Fire Detection System Configuration manual, Document ID A6V10333423, for details on programming.

  9. Check for proper operation.
Dialer FCA2015-U1 mounted on the back of the inner door (when used with a 3HU Enclosure)
Parts Supplied

Quantity

Type

1

DACT Board

4

Screws

1

Instruction Sheet

1

Serial Communication Cable

*4

1 ¾” x ¼” Hex Male to Female Standoff

*Used for FCM2019-U2/-U3 or FCM2035- U2/-U3 only.