Notice to users, installers, authorities having jurisdiction, and other involved parties:
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. | |||
Program feature or option | Permitted in UL 864? (Y/N) | Possible settings | Settings permitted in UL 864 |
PERIODIC TEST, PROGRAMMING RANGE | Y | 1 – 24 Hours | 1 – 6 Hours |
Digital Communication format | Y | SIA DCS, Ademco Contact ID, 3/1, 4/2 | SIA DCS, Ademco Contact ID |
This product incorporates field-programmable software. In order for the product to comply with the requirements in CAN/ULC-S527, Standard for Control Units and Accessories for Fire Alarm Systems, certain programming features or options must be limited to specific values or not used at all as indicated below. | |||
Program feature or option | Permitted in CAN/ULC-S527? (Y/N) | Possible settings | Settings permitted in CAN/ULC-S527 |
PERIODIC TEST, PROGRAMMING RANGE | Y | 1 – 24 Hours | 1 – 24 Hours |
Digital Communication format | Y | CID, SIA DCS | SIA DCS, Ademco Contact ID |