Mounted on a 4 inch octagonal equivalent.

Mounting The DB-11/-11C Base
Mounting The DB-11E Base

Refer to Figures 5 and 6, as applicable.

  1. Route all wires outward from outlet box.
  2. When ALARM LED viewing is critical, position the LED mark in the base in the intended direction.
  3. Route wires through the hole in the center of the base and mount base to outlet box. Make connections directly to the base terminals. Refer to Figures 1, 2 and 3 for details.
  4. After all bases are installed, check loop continuity. Refer to the System Manual for the loop continuity check procedure. check with OP121, OH121, HI121, use DBJ-11 Jumper Kit, P/N 500-699167 (between terminals 1a and 1b) to complete the loop. Do not use a jumper for FDO421/FDOOT441/FDOOTC441/FDOT421/FDT421/HI921/ OH921/OOH941/OOHC941/OP921 family devices.
  5. Continuity jumper must be removed from each base prior to installing detector.
  6. To insure proper installation of the detector head into the base:
    a. Route wires away from connector terminals.
    b. Take up all slack in the outlet box.
    c. Properly dress and position all wires flat against the base.
    d. Check that screw terminals are tight.