Prior to installation consider the following:
- Mounting height for visual and manual access to the Remote Person Machine Interface (PMI/PMI-2/PMI-3) displayed in the opening of the outer door.
- Weight and size of the enclosure.
- Local codes.
Install the backbox:
- Select a clean, dry, shock and vibration free surface.
- Position the backbox clear of obstructions so that the front door opens freely and the controls and indicators are easily accessible.
When preparing the opening to flush mount the REMBOX, make sure it does not exceed the dimensions of the enclosure. (Refer to the SPECIFICATIONS section for dimensions.)
- Mark the locations of the two upper mounting bolts of the backbox on the wall. (Refer to Figure 2.)
- Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt.
- Place the backbox over the two top bolts and allow it to slide down over the bolts.
- Mark, drill, and install the two bottom bolts in the backbox.
- Tighten all four bolts securely against the back wall of the backbox.