The ZAM-180 receives its control and communication data from the DAC-NET and sends its status data to the DAC-NET via the CAN Bus. Therefore it takes 1 sub-address of the DAC-NET.

The transmission of compressed or uncompressed audio data from the DAC-NET to the ZAM-180 is realized via ASI (Audio Serial Interface). Transmission on the ASI is executed with a timeslot method and is synchronized with Frame and Bit Synchronize Signals. Via control data on the CAN Bus, the timeslots are allocated to each ZAM-180. Each ZAM-180 is configured to listen to its corresponding timeslot.

A local audio input is provided to connect an external audio source. The audio input is isolated on the ZAM-180 to prevent ground loops. The local audio input is activated via an external contact. The control of this input will be executed by the amplifier directly. The ZAM-180 will send a message informing the DAC-NET that the ZAM-180 has turned on the local input. It is also possible to activate/ deactivate the local input on the control panel via CAN bus.

The speaker lines are individually supervised for open and short circuit. Ground fault is detected in common for both speaker lines on each ZAM-180.

The speaker lines are supervised in both the inactive and active state. The speakers must be AC-coupled.

Terminal Blocks, Controls and Indicators

Controls and Indicators

The ZAM-180 has one Reset button, seven diagnostic LEDs, level adaptation of the local external audio input and the CAN address switches, one terminal block, two terminal connections and two 60 pin flat ribbon connections as shown in Figure 2.

A reset switch is located on the top of the front panel. Pushing the reset switch re-initializes the ZAM-180 operation.

The LEDs functions are defined as follows:

LEDs Functions

LED

Color

Normal State

OFF Normal State

Action in OFF Normal State

POWER

green

ON

OFF –external voltages fail

Check for failure on PSC-12, CC-5, wiring

MODULE FAIL

yellow

OFF

ON –general trouble at ZAM-180

Failure on ZAM, ZAM-180 needs to be replaced

CAN FAIL

yellow

OFF

ON –CAN interface trouble

Failure on AIC, DAC-NET, CC-5 backplane or other CAN cards/modules

ASI FAIL

yellow

OFF

ON –ASI interface trouble

Failure on “ASI OUT“ and/or “ASI IN“ at this ZAM-180

ZONE ACTIVE

green

OFF

ON –Speaker zone active

Indicates normal operation on speaker zone

ZONE TRBL

yellow

OFF

ON –Speaker zone trouble, open circuit or short circuit

Check wires to the speakers, EOL resistor(s) and de-coupling capacitors on every speaker

ZONE GND FAULT

yellow

OFF

ON –unwanted earth ground connection on a speaker line

Check wires to the speakers for earth ground connections

OVERLOAD

yellow

OFF

ON

Refers to Local Audio input only: Press “DOWN” push button until “OVERLOAD” LED turns off and “NORMAL” LED turns on

NORMAL

green

ON

OFF

Refers to Local Audio input only: No audio signal or audio signal too high/low

LOW

yellow

OFF

ON

Refers to Local Audio input only: Press “UP” push button until “LOW” LED turns off and “NORMAL” LED turns on

Terminal Connections: These terminals are used for field wiring as shown in Figure 12-14.

Power Input: This terminal block is non power limited and can supply up to 12A. This Input is connected to the output terminal TB4 of the PSC-12/PSX-12 as shown in Figure 11.