AIC plugs perpendicularly into one slot in the CC-5 card-cage via two 96-pin DIN connectors and can occupy any slot in the card cage.

The AIC must not be installed directly adjacent to a ZAC-40 or ZAM-180. There must be at least one module or empty space in a CC-5/CC-2 card cage between the AIC and the ZAC-40 or ZAM-180.

Installing the AIC
  1. Insert the AIC card into the card guides right-side up (lettering on the front panel is legible). Slide the card in until the card edge connectors contact the receptacles on the motherboard. Verify that the DIN connectors of the card and the card-cage aligned properly. The card can only plug in one direction to the card cage, if it does not align, DO NOT FORCE the card.
  2. Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the card until the connectors seat in the receptacles on the motherboard.
  3. Secure with the captive screws.
  4. Power up the system and verify that the AIC power LED turns ON.