The SSD mounts directly onto a (user supplied) double gang or 4-inch switchbox. Refer to Figure 7.

Installing the SSD
NOTICE

The SSD must be installed in a dry, protected environment only.

Feed the field wiring from the double gang or 4-inch switchbox through the opening in the mounting plate. Secure the mounting plate to the switchbox with screws (user supplied).

Make the wiring connections to the mounting plate as shown in Figure 6.

Connect the supplied 8-pin cable from P1 on the mounting plate to P1 on the back of the SSD Assembly. Align the standards in the four corners of the mounting plate with the standards in the four corners of the SSD Assembly. Secure with the screws provided.

Peel off the backing on the self-adhesive strip on the back of the overlay that is located just below the cutout for the display. Insert the 3 bottom tabs on the appropriate overlay with the 3 corresponding slots in the bottom of the SSD Assembly. Slightly bend the overlay to align and insert the 3 top tabs into the 3 corresponding slots in the top of the SSD Assembly. Press the overlay to the SSD assembly just beneath the cutout for the SSD display so that the adhesive from the strip on the overlay adheres to the SSD assembly. Discard the remaining overlays, if applicable.

NOTICE

Be sure to route field wiring away from sharp projections, corners and internal components of the SSD.