Controls and Indicators

The back panel of the FMT contains four LEDs, two CAN address switches and one six-position jumper header, J1, as shown in Figure 2. Factory released FMTs are configured as primary, with all five jumpers installed.

The function of the LEDs are defined as follows:

LED Functions

PWR (Power)

Green

Normally ON. When illuminated, indicates that power for the FMT is applied to the module.

CPU (Card Fail)

Yellow

Normally OFF. When illuminated, indicates that the card microprocessor has failed.

CAN (CAN Fail)

Yellow

Normally OFF. When illuminated, indicates that the CAN communication with the FMT has terminated.

RSR (Riser Fail)

Yellow

Normally OFF. When illuminated, indicates that the riser between the FMT and the TZC-8B is faulted.