Before applying power to the RNI check the following:

  • Ensure that the 24VDC power input on TB1 is connected and that the polarity is correct.
  • Check the setting of S1. If the RNI is at the end of the HNET is must be set to on. If the RNI is in the middle of the HNET/XNET it must be set to off. If the HNET/XNET is not used the position of S1 does not matter.
  • Check the position of P5. It must be set to H for HNET or X for XNET.
  • Check the CAN termination. If the RNI is at the end of the CAN network, a CAN terminator (P/N110-134215, supplied with the NIC-C) must be installed into the last CAN module in the REMBOX.

If the RNI is in the middle of the CAN network no CAN terminators can be installed. If CAN is not used then the terminator can be stored in P4. It will be needed if CAN modules are added to the REMBOX at a later time. Refer to the NIC-C Installation Instructions P/N 315-033240 for examples of CAN installation and termination.

  • Check the setting of P7. If the local sound is required, make sure P7 is set to ON. Otherwise, set it to OFF.