P7 enables or disables an audible device similar to the CSB. This audible sounds whenever a switch is pressed on either the LVM, SCM-8 or the FCM-6. If this is not desired the audible can be silenced by changing the jumper installed on P7 to positions 2 and 3. P7 is configured in the factory (positions 1 and 2) to have the audible active.
S1 is used to terminate the HNET/XNET. If the RNI is installed at the end of an HNET network, S1 must be set to the ON position. If the RNI is in the middle of the HNET/XNET, set S1 to the OFF position.
P5 must be set to the HNET (H) position to select HNET or the XNET (X) position to select XNET. Only one network, either HNET or XNET, can be used.