The Model RNI from Siemens Industry, Inc., allows for the remote installation of the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular), Global PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) (on XNET), SSD-C-REM (on HNET), and the LVM/LCM-8/SCM-8/FCM-6/SIM-16/OCM-16 (on CAN) modules.
When used in a REMBOX4, the FMT and LVM are also supported.
The HNET/XNET can be wired either Style 4 or Style 7. The RNI must be placed in between two NIC-Cs when used in a Style 7 Network with the Global PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) (on XNET) or the SSD-C-REM (HNET). When using the PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular), the RNI may be located in the middle or at the end of the HNET. Refer to the table below for the allowable locations of modules at the end of a HNET or XNET.
| HNET | XNET | ||
| Style 4 | Style 7 | Style 4 | Style 7 |
SSD-C-REM | Y | N | * | * |
PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) (HNET) | Y | Y | * | * |
GLOBAL PMI/PMI-2/PMI-3 (XLS), FCM2041-U2 (Desigo Fire Safety Modular), FCM2041-U3 (Cerberus PRO Modular) (XNET) | * | * | Y | N |
N=Not allowed, Y=Allowed, *Not allowed on this network
The CAN network may only be wired Style 4. The RNI may be located at the end or in the middle of a CAN network. A 24VDC input is also required. This can be obtained from the PSC-12 power limited output (TB3). Audio signals for the LVM and FMT are connected to TB1 of the PSC-12. The RNI mounts in the rear of either the REMBOX2 or REMBOX4 enclosures. It can also be installed in a CAB1, CAB2, or CAB3 using the mounting plate RNI-CAB-BRKT. The RNI provides terminal blocks for all field wiring connections. Internal connections are made to plug in connectors specifically provided for each of the installed modules. The HNET/XNET and the CAN networks can be used simultaneously.